Liebert iCOM Display Components and Functions
Liebert
®
iCOM
®
for Liebert DSE
™
12
2.2.3 Entering a Password
The password must be entered before any value of the menu item parameter can be changed. There
are three levels of password for preventing unauthorized changes.
1. User menu password allows the operator the ability to change the parameters in the User menu.
The User menu password is 1490.
2. Service menu password enables the operator to changes parameters in both Service and User.
The Service menu password is 5010.
3. Advanced menu password allows the changes to be made in all parameters.
To enter a password:
1. Navigate to the menu that contains the parameter to be changed.
2. Select
Password
in the submenu by pressing the Enter key.
3. Press the Enter key to move your cursor to the right side of the screen to select the question
marks.
4. Use the arrow keys to enter the numeral for the password’s first digit (the up arrow key moves
from 1 to the next digit).
5. Use the right arrow key to move to the next question mark and repeat
to enter all digits in
the password.
6. After entering the password, press enter.
If the password is correct, the
Actual Level
shown to the right of
Password
will change
from 0 to 1 or 2. The menu will remain locked if the password was incorrect.
Figure 11 Entering a password
NOTE
Entering the Service menu password permits access to both the User and Service menus.
NOTE
Returning to the Status menu will require re-entering a password to make changes.