Service Menu Parameters
Liebert
®
iCOM
®
for Liebert DSE
™
144
Figure 128
Sensor calibration/setup screen, page 5 of 7
Figure 129
Sensor calibration/setup screen, page 6 of 7
S657 DP Transducer is Connected to
—Sets the analog input that will be used for the differential
pressure transducer. This parameter is selectable from None, Ana In 1, Ana In 2, Ana In 3 and
Ana In 4. The default is none.
S658 DP Transducer is Setup in
—Sets the unit of measure that will be used for the differential
pressure transducer. This parameter is selectable in inWC or PA. The default is PA.
S659 DP Transducer Low
—Sets the unit of measure that will be used for the low differential
pressure transducer. This parameter is selectable from 0-9.999 inWC. The default is 0.000 inWC.
S660 DP Transducer High
—Sets the unit of measure that will be used for the high differential
pressure transducer. This parameter is selectable from 0-9.999 inWC. The default is 2.005 inWC.
S661 Number of EC Fans
—Sets the unit of number of EC fans. This parameter is selectable
between 1 and 5. The default is 3.
S662 Inlet Ring K-Value
—Sets the inlet ring K-Value. This parameter is selectable between 1 and
999. The default is 480.