Service Menu Parameters
Liebert
®
iCOM
®
for Liebert DSE
™
114
Figure 88
Setpoints screen, page 7 of 9
S168 Fan Back Draft Control
—Enables or disables the Back Draft fan control. This feature allows
EC Fans (only) to operate at very low speeds to prevent airflow from cycling through the unit due to a
higher under-floor static pressure than the above floor static pressure. VFD’s cannot be used with this
feature due to motor and or bearing degradation that may occur at the low fan speeds required to
support this feature.
S169 VSD Setpoint BACK DRAFT
—The variable speed device setpoint is set as a voltage
reference. The lower the voltage, the slower the fans will spin. This parameter is set based on the
application. Higher under-floor static pressure may require a higher setting to prevent air flow
through the unit.
S171 Not Selectable Zone 1
—The not selectable Zone 1 and 2 are zones that the EC fans cannot
operate within due to vibration harmonics that the fans may introduce to the unit. These parameters
will be set from the factory based on model type and should not need adjusted in the field.
S172 Not Selectable Zone 2
—The not selectable zone 1 and 2 are zones that the EC fans cannot
operate within due to vibration harmonics that the fans may apply to the units frame. These
parameters will be set from the factory based on model type and should not need adjusted in the field.
S173 Stop BDR when System is Off
—The above is true when S173
Stop BDR when System is
Off
is set to “Yes.” If S173 is set to ‘No’ the BDR mode will not be interrupted, unless BDR is disabled
or the unit is restarted.
S174 Remote Off and BDR
(Liebert HPM
™
only)—Active when terminals factory supplied RSD 37
+ 38 are open. SFA fan wiring required for operation. Do not use this feature when the doing an fire
system with the RSD. Contact Liebert Services for assistance.
!
WARNING
Risk of electrical shock. Can cause injury and death.
Open all local and remote electric power disconnect switches and verify with a voltmeter that
power is Off before working within the electric connection enclosures.
Never use any of these functions—Remote Off, Display Off, BMS Off, LOC Off—in place of
lockout/tagout procedures.
Some internal components of Liebert cooling units require and receive power even during the
Unit Off mode of the Liebert iCOM.
The factory-supplied optional disconnect switch is inside the Liebert cooling unit. The line
side of this switch contains live high voltage.
The only way to ensure that there is NO voltage inside the unit is to install and open a remote
disconnect switch. Refer to the unit electrical schematic.
Follow all local codes.
Summary of Contents for Liebert iCOM
Page 2: ......
Page 169: ...Service Menu Parameters 161 Liebert iCOM for Liebert DSE Notes ...
Page 170: ...Service Menu Parameters Liebert iCOM for Liebert DSE 162 ...
Page 171: ......