User Menu Parameters
Liebert
®
iCOM
®
for Liebert DSE
™
96
Figure 70 Set alarms screen, page 3
U224-U233 High/Low Remote 01 - 10
— Sets the High and Low remote temperature sensor alarm
points individually for each sensor when the parameter separate thresholds is set to disabled. The
range for both parameters is 34°F to 210°F. The default setting for low alarm is 55°F. The default
setting for high alarm is 90°F.
Figure 71 Set alarms screen, page 4
U235 Static Pressure Messages
—Enables or disables the static pressure alarms.
U236 High Static Pressure
—Sets the pressure at which the High Static Pressure Alarm is
activated. This parameter is adjustable from 0.000 - 1.405 inWC. The default setting is 1.284 inWC.
U237 Low Static Pressure
—Sets the pressure at which the Low Static Pressure Alarm. This
parameter is adjustable from 0.000 - 1.395 inWC. The default setting is 0.000 inWC.
U238 SP Messages During Unit Off
—Enables or disables the static pressure alarms when the unit
is OFF.