Installation
21
Liebert
®
GXT4
™
User Manual
7. Verify the circuit breaker on the External Battery Cabinet is in the On position.
8. Use the included configuration program or the LCD to program the UPS with the number of external
battery cabinets connected. Instructions for the configuration program are in
The UPS is now equipped with additional backup battery run time. For approximate battery run times, refer
to
2.6 Connect Input/Output Power
The GXT4-5000RT208, Liebert GXT4-6000RT208 and Liebert GXT4-6000RTL630 are shipped with a
power distribution box attached. The Liebert GXT4-8000RT208 and Liebert GXT4-10000RT208 are
shipped with a cover plate over the power distribution connector.
Follow the instructions below for removal and installation.
2.6.1
Install the Power Distribution Box on 5000VA and 6000VA Models
1. Align the connectors and press the power distribution box onto the UPS.
2. Hold the box firmly against the UPS and tighten the captive screws except the one over the
maintenance bypass breaker.
3. Turn the output and input breakers On.
4. Start the UPS according to startup instructions.
5. Verify that the UPS lamp is illuminated.
6. Turn the maintenance bypass breaker Off.
7. Insert the maintenance bypass interlock bracket behind the captive screw and tighten the screw.
NOTE
When removing an external battery cabinet, the circuit breaker on the rear of the cabinet must be
turned off before disconnecting the cable.
NOTE
If the UPS is to be shipped or stored for an extended time, the connector should be disconnected.
This will minimize any standby current drain on the batteries and help attain their design life.
NOTE
Do not operate the UPS with the power distribution box removed. To shut off all power to this box
and to the load, utility input power must be disconnected.
NOTE
The maintenance bypass breaker interlock bracket must be installed behind the captive screw,
and the screw must be tightened for the UPS to operate in inverter mode.
Summary of Contents for Liebert GXT4-10000RT208
Page 1: ...Liebert GXT4 UPS 208 V 5000 VA 10 000 VA 6000RTL630 User Manual ...
Page 2: ......
Page 12: ...Glossary of Symbols Liebert GXT4 User Manual 4 Page intentionally left blank ...
Page 24: ...Product Description Liebert GXT4 User Manual 16 Page intentionally left blank ...
Page 36: ...Installation Liebert GXT4 User Manual 28 Page intentionally left blank ...
Page 52: ...Operation and Display Panel Liebert GXT4 User Manual 44 Page intentionally left blank ...
Page 70: ...Troubleshooting Liebert GXT4 User Manual 62 Page intentionally left blank ...
Page 79: ......