Electrical Connections—UPS
25
Liebert
®
APM
™
Figure 11 Busbars—External 600mm battery cabinet
.56" Dia.(14.3mm)
.44" Dia. (11.1mm)
1. All dimensions are in inches (mm).
2. Control wiring and power wiring must be run in separate conduits.
3. Copper cables onlyare recommended.
4. All wiring is to be in accordance with national and local electrical codes.
5. If battery cabinet is attached to UPS, Emerson will supply interconnect cables.
Top View
Bottom View
Left Side View
Panel Removed
Front View
Door Removed
Right Side View
Panel Removed
23.6"
(600mm)
37.5"
(953mm)
DC Connection
Busbars
Alber Battery
Monitoring
Ground
Bus
See
Detail A
78.7"
(2000mm)
UAM05020
Rev. 1
DETAIL A
3.66
"
(93mm)
3.66
"
(93mm)
3.66
"
(93mm)
1.75
"
(45mm)
1.75
"
(45mm)
1.75
"
(45mm)
1.75
"
(45mm)
1.75
"
(45mm)
1.65
"
(42mm)
1.65
"
(42mm)
4.96
"
(126mm)
TERMINAL SPECIFICATIONS
Unit Rating: 15-90kVA
Bolt Shaft Size: M10
Torque: 240 lb-In (27Nm)