IRM-S02TH Intelligent Temperature 

and Humidity Sensor User Manual 

1    Overview 

IRM-S02TH  intelligent temperature and  humidity sensor  (sensor  for short) is 
used  to  measure  and  display  environment  temperature  and  humidity.  It 
supports MODBUS  protocol  through  RJ45 port  in  RS-485 mode to configure 
and collect data. It is applicable for indoor sites which need temperature and 
humidity control such as communication rooms and IT data centers. 

1.1  Product Introduction 

1.1.1    Appearance 

The sensor’s appearance is shown as the following figure.

 

ALARM

Temp&Hum   Sensor

IRM-S02TH

Gro

u

p

  

Nu

m

DIP switch

RJ45 port

LCD display panel

Alarm indicator

Front view

Right view

12345678

RJ45 port

 

Size (height × width × depth): 97mm × 44mm × 22mm      Weight: about 100g 

1.1.2    RJ45 Port 

Two  RJ45  ports  are  used  in  the  electric  connection  of  the  sensor  for  power 
supply, communication and equipment connection in series.  The definition of 
RJ45 ports is shown in the following table.

 

Pin 

Pin1 and Pin2  Pin3 and Pin6 

Pin4 and Pin5 

Pin7 

Pin8 

Definition 

+12V/24V 

NC 

GND 

D+ 

D- 

 

1.1.3    DIP Switch 

The  DIP  switch  is  used  to  set  sensor  address  to  communicate  with  upper 
equipment  through  MODBUS  protocol.  The  sensor  address  is  composed  of 
group number and serial number within the group. The DIP1 ~ DIP4 are used 
to  set  the  group  number  and  the  DIP5  ~  DIP6  are  used  to  set  the  serial 
number  within  the  group.  For  example,  the  sensor  address  of  71  is  set  as 
shown in the following figure, among which 0111 means group number 7 and 
01 means serial number 1 within the group.

 

Group

Num

1 2 3 4 5 6

DIP

ON

0 1 1 1 0 1

Note: 1. DIP switch in the ON position means 1,
          or it means 0;

2. The sensor address cannot be set as 00,
which is the broadcast address.

 

The settings of DIP1 ~ DIP6 are listed in the following table. 

DIP1 ~ 

DIP4 

Group 

 

DIP1 ~ 

DIP4 

Group 

 

DIP1 ~ 

DIP4 

Group 

  DIP5 ~ 

DIP6 

Num 

0 0 0 0 

0 1 1 0 

1 1 0 0 

0 0 

0 0 0 1 

0 1 1 1 

1 1 0 1 

0 1 

0 0 1 0 

1 0 0 0 

1 1 1 0 

1 0 

0 0 1 1 

1 0 0 1 

1 1 1 1 

1 1 

0 1 0 0 

1 0 1 0 

 

 

 

 

0 1 0 1 

1 0 1 1 

 

 

 

 

 

1.1.4    LCD Display Panel 

The LCD display panel can display sensor address, temperature and humidity 
data  in  real  time.  Temperature  and  humidity  are  displayed  by  turns  every  2 
seconds.  For  example,  when  the  sensor address  is  71, and the temperature 
data  is  23.6°C,  the  LCD  display  panel  indicates  the  data  as  shown  in  the 
following figure.

   

Temperature data

Sensor address

Data unit

 

1.1.5    Alarm Indicator 

When  the  temperature  data  is  outside  the  the  configured  data  range  or  the 
sensor fails, the alarm indicator flashes; when the temperature data is in the 
range of the configured data, the alarm indicator extinguishes.

 

1.2    Technical Specification 

Technical Specification 

Description 

Operating voltage   

9Vdc ~ 28Vdc 

Power consumption 

0.2W 

 

Measurable temperature range 

-10°C ~ +50°C 

Measurable humidity range 

5% ~ 95%RH 

Temperature measuring precision 

±1°C (10°C ~ 30°C) 

±2°C (other temperature range) 

Humidity measuring precision 

±10%RH (40% ~ 60% RH) 

±20%RH (other humidity range) 

 

2    Installation 

2.1    Environment Requirement 

1.  Operating  environment  should  be  free  of  conductive  dust  and 
metal-corrosive & insulation-breaking gases. 

2. Avoid using the sensor in watery or foggy places. 

3. 

Keep  a  clearance  of  more  than  20mm  around  the  sensor’s  airway  to 

ensure ventilation inside and outside of the sensor. 

4.  Operating  temperature:  -10°C  ~  +50°C;  storage  temperature:  -30°C  ~ 
+70°C; humidity: 5% ~ 95% RH (non-condensing). 

2.2    Unpacking Inspection 

Unpack  the  sensor  and  visually  inspect  the  sensor’s  appearance.  If  any 
damage is found, please contact the carrier immediately. 

Check against the consignment list to make sure the sensor and accessories 
are complete and correct. 

2.3    Mechanical Installation 

Three  modes  are  available  for  the 

sensor’s  mechanical  installation.  The 

installation accessories and modes are shown in the following figure. 

Back installation hole

Magnet pothook

L pothook

T pothook

Sensor

Back installation hole

 

Mode one: Insert the magnet pothook into the sensor’s back installation hole, 
and the sensor can absorb on iron surface. 

Mode  two:  Insert  the  L  pothook  into  the  sensor’s  back  installation  hole,  and 
hang the pothook in the square hole of rack’s column with care.   

Mode  three:  Insert  the  T  pothook  into  the  sensor’s  back  installation  hole, 
insert the  bulge  of  the  T  pothook  into  the  installation slot  of the  rack’s basic 
frame, and rotate the sensor 90 degree clockwise with care. 

 

Note 

The sensor can not only be installed through the three kinds of accessories above, but 
also can hang on fixed screws directly through the installation hole. 

 

2.4    Cable Connection 

Insert one end of the standard straight 

network cable into the sensor’s RJ45 

port,  and  insert  the  other  end  into  the  sensor  appropriative  port  of  upper 
equipment or sensor in series. 

3    Maintenance 

1. To clean the sensor, you should cut off the power and use a piece of soft 
cloth to wipe it. 

2. Do not

 

disassemble the sensor, or the inside subtle parts may be damaged. 

Emerson Network Power Co., Ltd. 

Address:  No.1 Kefa  Rd.,  Science &  Industry  Park,  Nanshan  District  518057, 
Shenzhen China 

Homepage: www.emersonnetworkpower.com.cn 

E-mail[email protected] 

Copyright © 2009 by Emerson Network Power Co., Ltd. 

All  rights  reserved.  The  contents  in  this  document  are  subject  to  change 
without notice. 

Version    V1.4        Revision date    July 14, 2009        BOM    31011979 