Section 1: Introduction
Introduction
Section 1: Introduction
This manual contains specifications, installation, operating, and maintenance information for
Communication Adapter Module (CAM216/16) Model No. 6 with HART option.
The CAM16 is used with Valve Automation M2CP, MPA, HQDCM33 and EHO valve actuators,
whereas the CAM216 is used with the TEC2, TEC2000 and Model 500. Functionality of the
actuator using the HART option supports both block valve (On/Off control) and modulating/
positioning control. This manual also describes actuator setup using the HART specified
Device Description (DD), parameter access, and methods. Display and control using these
parameters depend on the SCADA or DCS host software being used. Refer to the host software
documentation for information on executing methods and accessing parameters.
1.1
HART CAM16/216 Specifications
Table 1.
Card and Device Type
Product Name
Expanded Device Type
Applicable Devices
CAM16
0xE28B (Hex)
M2CP
MPA
HQ
CAM216
0xE28C (Hex)
Model 500
TEC2000
TEC2
EHO
Table 2.
General Device Information
Type
Specifications
Manufacturer Name
Valve Automation
Manufacturer ID
0x6060 (Hex)
HART Protocol Revision
7.5
Device Revision
01
DD Revision
01
Table 3.
HART Device Variables
Device Variable Code
Device Variable Name
Units
0
Setpoint
%
1
Position
%
2
Torque
%
3
Analog Input 1
%
4
Analog Input 2
%
5
Analog Output 1
%
6
Analog Output 2
%
7
Hydraulic Pressure
PSI (Pounds Per Square Inch)
8
Accumulator Pressure
PSI (Pounds Per Square Inch)