Troubleshooting
8-5
To reflash the configuration data file:
1.
Select
Transfer Data
from the Config600 software.
2.
Choose the Comm port connected to the S600+. Default parameters
for serial ports are 38400 bps, 8 data bits, 1 stop bit, and no parity.
Note
:
You can also transfer configuration files using the Ethernet
connection, as well as the serial communications port.
3.
Select the required configuration file and the sections you want to
transfer to the S600+.
4.
Click
Send Now
to download the file to the S600+.
Once the download completes, the S600+ restarts and displays the
Startup menu.
8.3.3 Clear SRAM
The Factory Setup option on the Startup menu includes
Clear SRAM
and
Format Flash
options. Use these options only under instruction
from factory personnel in the event of a problem.
Use
Clear SRAM
to overwrite the S600+’s SRAM area. With this
option, you lose all battery-backed configuration data, including
system configuration data, process configuration data, metering
totalisers, and network settings.
Following a
Clear SRAM
command, the S600+ restarts and redisplays
the Startup menu. You cannot warm start the S600+ again until you
download a full configuration from a PC running Config600 software.
To clear SRAM:
1.
Select
FACTORY SETUP
from the Startup menu.
2.
Select
CLEAR SRAM
.
3.
Press
1
to confirm the selection. The following message displays:
COMMUNICATIONS LINK FAILURE
4.
Wait 30 seconds. If the display has not changed after 30 seconds,
reboot the S600+ (power down, wait five seconds, and then
repower). The Startup menu displays when the process completes.