Introduction

This installation guide provides instructions for 

installation, startup and adjustment. To receive a 

copy of the instruction manual, contact your local 

Sales Office or view a copy at www.fisher.com. 

For further information refer to: Type 289P 

Instruction Manual, D102680X012.

PED Categories

This product may be used as a pressure accessory 

with pressure equipment in the following Pressure 

Equipment Directive categories. It may also be used 

outside of the Pressure Equipment Directive using 

sound engineering practice (SEP) per table below. 

For information on the current PED revision see 

Bulletin: 

D103053X012

.

PRODUCT SIZE

CATEGORIES

FLUID TYPE

DN 25 / NPS 1

SEP

1

Specifications

Maximum Relief (Inlet) Pressure

(1)(2)

1 NPT:

 3.4 bar / 50 psig over relief set pressure or 

7.6 bar / 110 psig whichever is lower

2 NPT:

 1.0 bar / 15 psig

Relief Set Pressure Ranges

1 NPT

Type 6358B Pilot:

 0.69 to 6.9 bar / 10 to 100 psig

2 NPT

Type 6365 Pilot:

 35 mbar to 0.14 bar / 

14 in. w.c. to 2 psig

Type 6368B Pilot:

 0.14 to 0.69 bar / 2 to 10 psig

Proof Test Pressure

All Pressure Retaining Components have been 

proof tested per Directive

Temperature Capabilities

(1)

Nitrile (NBR):

 -29 to 82°C / -20 to 180°F

Fluorocarbon (FKM):

 -18 to 149°C / 0 to 300°F

Installation

!

WARNING

Only qualified personnel shall install 

or service a relief valve. Relief 

valves should be installed, operated 

and maintained in accordance with 

international and applicable codes and 

regulations and Emerson Process 

Management Regulator Technologies, 

Inc. instructions.
If using a relief valve on a hazardous 

or flammable fluid service, personal 

injury and property damage could 

occur due to fire or explosion 

of vented fluid that may have 

accumulated. To prevent such injury 

or damage, provide piping or tubing to 

vent the fluid to a safe, well-ventilated 

area or containment vessel. Also, when 

venting a hazardous fluid, the piping 

or tubing should be located far enough 

away from any buildings or windows 

so to not create a further hazard and 

the vent opening should be protected 

against anything that could clog it.
Personal injury, equipment damage 

or leakage due to escaping fluid 

or bursting of pressure-containing 

parts may result if this relief valve is 

overpressured or is installed where 

service conditions could exceed the 

limits given in the Specifications 

section or where conditions exceed 

any ratings of the adjacent piping or 

piping connections.
To avoid such injury or damage, 

provide pressure-relieving or 

pressure-limiting devices (as required 

by the appropriate code, regulation 

or standard) to prevent service 

conditions from exceeding limits.
Additionally, physical damage to the 

relief valve could result in personal 

injury and property damage due to 

escaping fluid. To avoid such injury 

and damage, install the relief valve in a 

safe location.

Clean out all pipelines before installation of the 

relief valve and check to be sure the relief valve 

has not been damaged or has collected foreign 

material during shipping. For NPT bodies, apply pipe 

compound to the external pipe threads. For flanged 

bodies, use suitable line gaskets and approved 

piping and bolting practices. Install the relief valve 

in any position desired, unless otherwise specified, 

but be sure flow through the body is in the direction 

indicated by the arrow on the body.

1. The pressure/temperature limits in this Installation Guide and any applicable standard or code limitation should not be exceeded.

2. Relief pressure plus maximum allowable build-up over setting.

Type 289P

Installation Guide

D102680X014
English – July 2017

Summary of Contents for Fisher Type 289P

Page 1: ...have accumulated To prevent such injury or damage provide piping or tubing to vent the fluid to a safe well ventilated area or containment vessel Also when venting a hazardous fluid the piping or tubing should be located far enough away from any buildings or windows so to not create a further hazard and the vent opening should be protected against anything that could clog it Personal injury equipm...

Page 2: ...est gauge during the adjustment Replace closing cap or tighten the locknut to maintain the desired setting Taking Out of Service Shutdown WARNING To avoid personal injury resulting from sudden release of pressure isolate the relief valve from all pressure before attempting disassembly If pressure is introduced first to the main valve before the pilot the main valve may go wide open and subject the...

Page 3: ...asket 20 Restriction Plated carbon steel No 70 drill size or 0 71 mm 0 028 in diameter standard indicated by H for high gain stamped on pilot body and yellow color code 36 Connector Cap Gasket Figure 2 2 NPT Type 289P Main Valve Assembly 14A8406 26A0323 Figure 1 1 NPT Type 289P Main Valve Assembly APPLY LUBRICANT L SEALANT S 1 Recommended spare part 1 Lubricant and sealant must be selected such th...

Page 4: ...on logo is a trademark and service mark of Emerson Electric Co All other marks are the property of their prospective owners Fisher is a mark owned by Fisher Controls International LLC a business of Emerson Automation Solutions The contents of this publication are presented for information purposes only and while effort has been made to ensure their accuracy they are not to be construed as warranti...

Reviews: