Transducer Block
December 2009
4-35
PD Inside Status
PD Inside Status shows the status of Performance
Diagnostics.
PD Run
PD Run enables or disables Performance Diagnostics
in the instrument (PD Inside). Selecting PD Off
disables PD Inside. Selecting PD On enables PD
Inside.
Performance Critical
Performance Critical Alert
This alert is active if the instrument is no longer able to
control the valve or performance has been
dramatically reduced.
Performance Critical Alert Enable
When enabled Performance Critical Alert Enable
activates the Performance Critical Alert.
Performance Reduced
Performance Reduced Alert
This alert is active if the instrument has detected a
reduction in performance.
Performance Reduced Alert Enable
When enabled Performance Reduced Alert Enable
activates the Performance Reduced Alert.
Performance Information
Performance Information Alert
This alert is active if the instrument has detected a
condition that may pertain to control performance.
Performance Information Alert Enable
When enabled Performance Information Alert Enable
activates the Performance Information Alert.
PlantWeb Alert Enable
(TB
>
Configure/Setup
>
Detailed Setup
>
Alerts
>
PlantWeb Alert Enable)
Failed Enable
Failed Enable (FAILED_ENABLE [62]) enables or
disables conditions that can cause a failed alert. A
failed alert indicates a failure within the device that will
make the device or some part of the device
non-operational. Table C-2 lists the available
PlantWeb alerts.
Maintenance Enable
Maintenance Enable (MAINT_ENABLE [63]) enables
or disables conditions that can cause a maintenance
alert. A maintenance alert indicates the device or
some part of the device needs maintenance soon.
Table C-2 lists the available PlantWeb alerts.
Advise Enable
Advise Enable (ADVISE_ENABLE [64]) enables or
disables conditions that can cause an advisory alert.
An advisory alert indicates informative conditions that
do not have a direct impact on the device’s primary
functions. Table C-2 lists the available PlantWeb
alerts.
PlantWeb Alert Reporting
(TB
>
Configure/Setup
>
Detailed Setup
>
Alerts
>
PlantWeb Alert Reporting)
Failed Suppress
Failed Suppress (FAILED_MASK [65]) determines
which of the failed alert conditions are suppressed so
that they are not reported. Even if reporting is
suppressed, the bit in Failed Active (FAILED_ACTIVE
[59]) is still set.
Maintenance Suppress
Maintenance Suppress (MAINT_MASK [66])
determines which of the maintenance alert conditions
are suppressed so that they are not reported. Even if
reporting is suppressed, the bit in Maintenance Active
(MAINT_ACTIVE [60]) is still set.
Advise Suppress
Advise Suppress (ADVISE_MASK [67]) determines
which of the advise alert conditions are suppressed so
that they are not reported. Even if reporting is
suppressed, the bit in Advise Active
(ADVISE_ACTIVE [61]) is still set.
Instrument
(TB > Configure/Setup > Detailed Setup
>
Instrument)
Tag Description
The Tag Description (TAG_DESC [2]) is a 32
character description used to assign a unique
description to each block within the digital valve
controller to describe the intended application for the
block.
Pressure Units
Define the output and supply pressure units
(PRESSURE_UNITS [90]) in either psi, bar, or kPa.
4
Summary of Contents for Fisher FIELDVUE DVC6000f
Page 54: ...DVC6000f Digital Valve Controllers December 2009 2 30 2 ...
Page 62: ...DVC6000f Digital Valve Controllers December 2009 4 2 4 ...
Page 127: ...Transducer Block December 2009 4 67 4 ...
Page 141: ...AO Function Block December 2009 4 81 4 ...
Page 207: ...MAI Function Block December 2009 4 147 4 ...
Page 219: ...DO Function Block December 2009 4 159 4 ...
Page 231: ...DI Function Block December 2009 4 171 4 ...
Page 302: ...DVC6000f Digital Valve Controllers December 2009 8 16 8 ...
Page 306: ...DVC6000f Digital Valve Controllers December 2009 A 4 A ...
Page 350: ...DVC6000f Digital Valve Controllers December 2009 E 6 E ...
Page 368: ...DVC6000f Digital Valve Controllers December 2009 F 18 F ...
Page 372: ...DVC6000f Digital Valve Controllers December 2009 Glossary 4 Notes G Glossary ...
Page 382: ...DVC6000f Digital Valve Controllers December 2009 Index 10 F Index ...