Table 3-2. Actuator Information for Basic Setup
Actuator
Manufacturer
Actuator
Model
Actuator Size
Actuator Style
Starting
Tuning
Set
Feedback
Connection
Travel Sensor Motion
(Relay A or C)
(1)
Fisher
585C & 585CR
25
50, 60
68, 80
100, 130
Piston Dbl w/ or w/o
Spring. See actuator
instruction manual and
nameplate.
F
J
L
M
SStem Pot for
travels up to
4 inches. SStem
Roller Pot for
longer travels
Depends upon pneumatic connections.
See description for Travel Sensor
Motion
657
30
34, 40
45, 50
46, 60, 70, 76,
& 80-100
Spring & Diaphragm
H
K
L
M
SStem Pot
Clockwise
667
30
34, 40
45, 50
46, 60, 70, 76,
& 80-100
Spring & Diaphragm
H
K
L
M
SStem Pot
Counterclockwise
1051 & 1052
20, 30
33
40
60, 70
Spring & Diaphragm
H
I
K
M
RShaft Pot
Clockwise
1061
30
40
60
68, 80, 100 &
130
Piston Dbl w/o Spring
J
K
L
M
RShaft Pot
Depends upon pneumatic connections.
See description for Travel Sensor
Motion
1066
20, 27, 75
Piston Dbl w/o Spring
Specify
RShaft Pot
Depends upon pneumatic connections.
See description for Travel Sensor
Motion
1066SR
20
27, 75
Piston Sgl w/Spring
G
L
RShaft Pot
Mounting Style
Travel Sensor
Motion
A
Clockwise
B
Counterclockwise
C
Counterclockwise
D
Clockwise
2052
1
2
Spring & Diaphragm
J
K
RShaft Pot
Clockwise
3024
GA 1.21
GA 1.31
GA 1.41
Spring & Diaphragm
E
H
K
SStem Pot
For P
o
operating mode (air opens),
Counterclockwise
For P
s
operating mode (air closes),
Clockwise
3025
P460, P462,
P900
M
RShaft Pot
Specify
GX
225
Spring & Diaphragm
X
(2)
SStem Pot
Air to
750
K
Open
Close
1200
M
Counterclockwise
Clockwise
Baumann
Air to Extend
16
32
70
Spring & Diaphragm
C
E
K
SStem Pot
Clockwise
Air to Retract
16
32
70
Spring & Diaphragm
C
E
K
SStem Pot
Counterclockwise
Rotary
10
25
54
E
H
J
RShaft Pot
Specify
1. Values shown are for relay A and C. Reverse for relay B.
2. X = Expert tuning. Proportional Gain = 4.2; Velocity Gain = 3.0; Minor Loop Feedback Gain = 18.0
3
Summary of Contents for Fisher FIELDVUE DVC6000f
Page 54: ...DVC6000f Digital Valve Controllers December 2009 2 30 2 ...
Page 62: ...DVC6000f Digital Valve Controllers December 2009 4 2 4 ...
Page 127: ...Transducer Block December 2009 4 67 4 ...
Page 141: ...AO Function Block December 2009 4 81 4 ...
Page 207: ...MAI Function Block December 2009 4 147 4 ...
Page 219: ...DO Function Block December 2009 4 159 4 ...
Page 231: ...DI Function Block December 2009 4 171 4 ...
Page 302: ...DVC6000f Digital Valve Controllers December 2009 8 16 8 ...
Page 306: ...DVC6000f Digital Valve Controllers December 2009 A 4 A ...
Page 350: ...DVC6000f Digital Valve Controllers December 2009 E 6 E ...
Page 368: ...DVC6000f Digital Valve Controllers December 2009 F 18 F ...
Page 372: ...DVC6000f Digital Valve Controllers December 2009 Glossary 4 Notes G Glossary ...