![Emerson Fisher FIELDVUE DVC6000f Instruction Manual Download Page 222](http://html.mh-extra.com/html/emerson/fisher-fieldvue-dvc6000f/fisher-fieldvue-dvc6000f_instruction-manual_102337222.webp)
DVC6000f Digital Valve Controllers
December 2009
4-162
Invert Option
Alarm Detection
Figure 4-31. Discrete Input Function Block Schematic
FIELD_VAL_D
MODE
SIMULATE
PV_D
OUT_D
Discrete Signal
Table 4-76. Channel Selection for the Discrete Input Function Block
Selection
Transducer Block Parameter
(1)
Transducer Block
Index Number
Bit Number
(2)
23
TRAVEL_D
33
N/A
24
INST_ALERTS_ACTIVE:PROX_ACTIVE
74.5
0: Travel Open
25
INST_ALERTS_ACTIVE:PROX_ACTIVE
74.5
1: Travel Closed
26
INST_ALERTS_ACTIVE:TRAVEL_ACTIVE
74.4
2: Travel Limit Lo Lo
27
INST_ALERTS_ACTIVE:TRAVEL_ACTIVE
74.4
4: Travel Limit Lo
28
INST_ALERTS_ACTIVE:TRAVEL_ACTIVE
74.4
3: Travel Limit Hi
29
INST_ALERTS_ACTIVE:TRAVEL_ACTIVE
74.4
1: Travel Limit Hi Hi
30
INST_ALERTS_ACTIVE:PROX_ACTIVE
74.5
5: Proximity Lo Lo
31
INST_ALERTS_ACTIVE:PROX_ACTIVE
74.5
4: Proximity Lo
32
INST_ALERTS_ACTIVE:PROX_ACTIVE
74.5
3: Proximity Hi
33
INST_ALERTS_ACTIVE:PROX_ACTIVE
74.5
2: Proximity Hi Hi
1. Refer to table 4-13 for parameter descriptions.
2. See pages 4-31 and 4-33, Travel ALerts and Prox Alerts, for information on accessing these alerts. Refer to Appendix F for information on accessing these alerts through DeltaV.
Valve Travel
Channel 23 provides valve travel.
0 = Closed, 1 = 100% open, 5 = 5% open, 10 = 10%
open, 15 = 15% open, etc.
Open/Closed Limit Switch
Channels 24 and 25 provide valve open and closed
limit switch functionality for the DI block. These
channels will detect if the valve position is more than
the Travel Open Alert Point for open detection or less
than the Travel Closed Alert Point for closed detection.
These channels provide an adjustable deadband to
clear the detected position.
0= Not Active, 1= Active
Variable Limit Switch
Channels 26 through 29 provide variable limit switch
functionality for the DI block. Trip points for this limit
switch functionality are based on the Travel Alert
settings in the transducer Block. The DI function block
provides the same type of position detection as the
travel alerts in the transducer block. Table 4-77 lists
the transducer block parameters used with DI block
channels 26 through 29. Refer to Travel and Prox, on
page 4-31 for more information on the transducer
block travel alerts.
0= Not Active, 1= Active
4
Summary of Contents for Fisher FIELDVUE DVC6000f
Page 54: ...DVC6000f Digital Valve Controllers December 2009 2 30 2 ...
Page 62: ...DVC6000f Digital Valve Controllers December 2009 4 2 4 ...
Page 127: ...Transducer Block December 2009 4 67 4 ...
Page 141: ...AO Function Block December 2009 4 81 4 ...
Page 207: ...MAI Function Block December 2009 4 147 4 ...
Page 219: ...DO Function Block December 2009 4 159 4 ...
Page 231: ...DI Function Block December 2009 4 171 4 ...
Page 302: ...DVC6000f Digital Valve Controllers December 2009 8 16 8 ...
Page 306: ...DVC6000f Digital Valve Controllers December 2009 A 4 A ...
Page 350: ...DVC6000f Digital Valve Controllers December 2009 E 6 E ...
Page 368: ...DVC6000f Digital Valve Controllers December 2009 F 18 F ...
Page 372: ...DVC6000f Digital Valve Controllers December 2009 Glossary 4 Notes G Glossary ...
Page 382: ...DVC6000f Digital Valve Controllers December 2009 Index 10 F Index ...