DVC6000f Digital Valve Controllers
December 2009
4-124
Table 4-47. Output Splitter Function Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Description
Initial
Value
Range
Block
Mode
RO /
RW
Index
Number
Output 2 Range
OUT_2_RANGE
11
RO
EU at 100%
EU at 0 %
Unit Index
Decimal Point
100
0
%
2
Data Type: DS-68
The high and low scale values, engineering units code,
and number of decimal places to be used in displaying the
OUT value, this parameter has not effect on this block.
Grant Deny
GRANT_DENY
12
Data Type: DS-70
Options for controlling access of host computers and local
control panels to operating, tuning, and alarm parameters
of the block. GRANT:0=N/A, 1=granted
DENY: 0=N/A, 1= denied
GRANT
12.1
N/A
0: Program
1: Tune
2: Alarm
3: Local
All bits: 0
DENY
12.2
N/A
All bits: 0
Status Options
STATUS_OPTS
13
OOS
1: IFS if BAD
CAS_IN
All bits: 0
Data Type: Bit String
0=Disabled 1=Enabled
User option for status
Cascade Input
CAS_IN
14
Status
BAD:
NC:
const
Data Type: DS-65
The remote setpoint from another block.
Value
0
Back Calculation Output
BKCAL_OUT
15
RO
Status Limits
Data Type: DS-65
Output value to another block for backwards output
tracking.
Input Array
IN_ARRAY
16
All: 0
Data Type: Float
Used with OUT_ARRAY to map input to output. See Input
to Output Mapping, page 4-119.
Output Array
OUT_ARRAY
17
All: 0
Data Type: Float
Used with IN_ARRAY to map input to output. See Input to
Output Mapping, page 4-119.
Lockval
LOCKVAL
18
0=Undfined
1=no lock
2=lock
0=
Undefined
Data Type: Enum
Used with OUT_ARRAY to map input to output. See Input
to Output Mapping, page 4-119.
Back Calculation Input 1
BKCAL_1_IN
19
Status
BAD:
NC:
const
Data Type: DS-65
The value and status reflecting the BKCAL_OUT of the
lower block associated with OUT_1. It is used for
initialization and to prevent windup in upstream blocks.
Value
0
Back Calculation Input 2
BKCAL_2_IN
20
Status
BAD:
NC:
const
Data Type: DS-65
The value and status reflecting the BKCAL_OUT of the
lower block associated with OUT_2. It is used for
initialization and to prevent windup in upstream blocks.
Value
0
Balance Time
BAL_TIME
21
Positive
0
Data Type: Float
Specifies the time for the internal working value of bias or
ratio to return to the operator set bias or ratio, in seconds.
Hystval
HYSTVAL
22
Update Event
UPDATE_EVT
23
RO
N/A
Data Type: DS-73
This alert is generated by any change to the static data.
UNACKNOWLEDGED
23.1
RW
N/A
0
=
Undefined
1
=
Acknowledged
2
=
Unacknowledged
0
=
Undefined
UPDATE STATE
23.2
RO
N/A
0
=
Undefined
1
=
Update Reported
2
=
Updated not
reported
0
=
Undefined
TIME_STAMP
23.3
RO
N/A
0
STATIC_REVISION
23.4
RO
N/A
0
RELATIVE_INDEX
23.5
RO
N/A
0
−
Continued
−
4
Summary of Contents for Fisher FIELDVUE DVC6000f
Page 54: ...DVC6000f Digital Valve Controllers December 2009 2 30 2 ...
Page 62: ...DVC6000f Digital Valve Controllers December 2009 4 2 4 ...
Page 127: ...Transducer Block December 2009 4 67 4 ...
Page 141: ...AO Function Block December 2009 4 81 4 ...
Page 207: ...MAI Function Block December 2009 4 147 4 ...
Page 219: ...DO Function Block December 2009 4 159 4 ...
Page 231: ...DI Function Block December 2009 4 171 4 ...
Page 302: ...DVC6000f Digital Valve Controllers December 2009 8 16 8 ...
Page 306: ...DVC6000f Digital Valve Controllers December 2009 A 4 A ...
Page 350: ...DVC6000f Digital Valve Controllers December 2009 E 6 E ...
Page 368: ...DVC6000f Digital Valve Controllers December 2009 F 18 F ...
Page 372: ...DVC6000f Digital Valve Controllers December 2009 Glossary 4 Notes G Glossary ...
Page 382: ...DVC6000f Digital Valve Controllers December 2009 Index 10 F Index ...