Transducer Block
December 2009
4-63
Table 4-13. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Description
Protect
Category
Initial Value
Range
Mode
RO /
RW
Index
Number
Temperature Units
TEMPERATURE_UNITS
89
RW
ALL
C=1001
F=1002
C
SETUP
Data Type: Enum (Uint8)
Pressure Units
PRESSURE_UNITS
90
RW
ALL
kPa=1133
bar=1137
psig=1143
inHg=1155
inH2O=1146
Kg/cm
2
=1145
kPa
SETUP
Data Type: Enum (Uint8)
Travel Units
TVL_UNITS
91
RW
ALL
cm=1012
mm=1013
in=1019
deg=1005
mm
SETUP
Data Type: Enum (Uint8)
Travel units for spec sheet
ACTUAL_TRAVEL and
RATEDTRAVEL only.
Length Units
LENGTH_UNITS
92
RW
ALL
cm=1012
mm=1013
in=1019
mm
SETUP
Data Type: Enum (Uint8)
Not used for spec sheet
ACTUAL_TRAVEL OR
RATEDTRAVEL
Area Units
AREA_UNITS
93
RW
ALL
cm
2
=1025
mm
2
=1027
in
2
=1030
cm
2
SETUP
Data Type: Enum (Uint8)
Spring Rate Units
SPRING_RATE_UNITS
94
RW
ALL
N/m=1165
lb/in=1596
N/m
SETUP
Data Type: Enum (Uint8)
MAI_CHANNEL_MAP
95
Data Type:Uint16 This defines
which transducer block channels
will be sent to each of the 8 MAI
channels. No scaling or other
conversion will be done. Values will
be sent in the currently defined
units. If set to 0, then no output to
MAI (status will be set to BAD).
1=FINAL_VALUE
2=TRAVEL_TARGET
3=FINAL_POSITION_VALUE
4=TRAVEL
5=SUPPLY_PRESS
6=ACT_PRESS_A
7=ACT_PRESS_B
8=ACT_PRESS_DIFF
9=DRIVE_SIGNAL
10=TRAVEL_DEVIATION
11=TEMPERATURE
12=CYCLE_COUNT
13=TRAVEL_ACCUM
MAI Channel 1
MAI_CHANNEL_1
95.1
RW
MAN,
OOS
1 through 13
1
SETUP
MAI Channel 2
MAI_CHANNEL_2
95.2
RW
MAN,
OOS
1 through 13
2
SETUP
MAI Channel 3
MAI_CHANNEL_3
95.3
RW
MAN,
OOS
1 through 13
3
SETUP
MAI Channel 4
MAI_CHANNEL_4
95.4
RW
MAN,
OOS
1 through 13
4
SETUP
MAI Channel 5
MAI_CHANNEL_5
95.5
RW
MAN,
OOS
1 through 13
5
SETUP
MAI Channel 6
MAI_CHANNEL_6
95.6
RW
MAN,
OOS
1 through 13
6
SETUP
MAI Channel 7
MAI_CHANNEL_7
95.7
RW
MAN,
OOS
1 through 13
7
SETUP
MAI Channel 8
MAI_CHANNEL_8
95.8
RW
MAN,
OOS
1 through 13
8
SETUP
Output Block Selection
OUTBLOCK_SEL
96
RW
MAN,
OOS
1: AO Block
2: DO Block
1: AO Block
SETUP
Data Type: Enum (Uint8)
Controls which output block (AO or
DO) the transducer block will
respond to.
PlantWeb Alerts Set PV Status
PWA_SET_STATUS
97
RW
MAN,
OOS
1: No
2: Yes
1: No
SETUP
Data Type: Enum (Uint8)
Controls whether the status of the
PV fed back to the output block
from the transducer block will be
affected by an active PlantWeb
alert.
Block Information
BLOCK_INFO
98
RO
0: Travel feedback
sensor detected
1: Output Block
Scheduled
2: Trigger Capturing
3: Output Block in
Normal Mode
4: Write Lock is on
5: Resource Block in
Auto Mode
Data Type: Bit String (2 bytes)
Reserved B
RESERVED_B
99
RW
Data Type: Bit String (4 bytes)
Travel Always
TRAVEL_ALWAYS
100
RO
Data Type: DS
−
65
4
Summary of Contents for Fisher FIELDVUE DVC6000f
Page 54: ...DVC6000f Digital Valve Controllers December 2009 2 30 2 ...
Page 62: ...DVC6000f Digital Valve Controllers December 2009 4 2 4 ...
Page 127: ...Transducer Block December 2009 4 67 4 ...
Page 141: ...AO Function Block December 2009 4 81 4 ...
Page 207: ...MAI Function Block December 2009 4 147 4 ...
Page 219: ...DO Function Block December 2009 4 159 4 ...
Page 231: ...DI Function Block December 2009 4 171 4 ...
Page 302: ...DVC6000f Digital Valve Controllers December 2009 8 16 8 ...
Page 306: ...DVC6000f Digital Valve Controllers December 2009 A 4 A ...
Page 350: ...DVC6000f Digital Valve Controllers December 2009 E 6 E ...
Page 368: ...DVC6000f Digital Valve Controllers December 2009 F 18 F ...
Page 372: ...DVC6000f Digital Valve Controllers December 2009 Glossary 4 Notes G Glossary ...
Page 382: ...DVC6000f Digital Valve Controllers December 2009 Index 10 F Index ...