Table 4-13. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Description
Protect
Category
Initial Value
Range
Mode
RO /
RW
Index
Number
INST_ALERTS_CONFIG2
77
Travel Deviation Alert Point
TVL_DEV_ALRT_PT
77.1
RW
ALL
>
0%,
<
= 125%
5%
SETUP
Data Type: Float
Alerts when difference between sp
and pv is too large for too long.
Travel Deviation Time
TVL_DEV_TIME
77.2
RW
ALL
>
= 0,
<
= 120 seconds
10 sec
SETUP
Data Type: Float
Travel Deviation Deadband
TVL_DEV_DB
77.3
RW
ALL
>
= 0%,
<
= 100%
2%
SETUP
Data Type: Float
Travel Accumulator Alert Point
TVL_ACCUM_ALRT_PT
77.4
RW
ALL
>
= 0
1,000,000
SETUP
Data Type: Uint32
Alerts when accumulated travel is
too much
Travel Accumulator Deadband
TVL_ACCUM_DB
77.5
RW
ALL
0
−
100%
1%
SETUP
Data Type: Float
Deadband
Cycle Count Alert Point
CYCLE_COUNT_ALRT_PT
77.6
RW
ALL
>
= 0
1,000,000
SETUP
Alerts when number of cycles is too
large.
Cycle Count Deadband
CYCLE_COUNT_DB
77.7
RW
ALL
0
−
100%
1%
SETUP
Data Type: Float
Deadband
Travel Open Alert Point
TVL_OPEN_ALRT_PT
77.8
RW
ALL
−
25% to 125%
99.5%
SETUP
Data Type: Float
Alert when valve is open. Control
DI channel 24 regardless of alert
enable state.
Travel Open Deadband
TVL_OPEN_DB
77.9
RW
ALL
>
= 0%,
<
=100%
1%
SETUP
Data Type: Float
Deadband
Travel Closed Alert Point
TVL_CLOSED_ALRT_PT
77.10
RW
ALL
−
25% to 125%
0.5%
SETUP
Data Type: Float
Alerts when valve closed. Controls
DI channel 25 regardless of alert
enable state.
Travel Closed Deadband
TVL_CLOSED_DB
77.11
RW
ALL
>
= 0%,
<
= 100%
1%
SETUP
Data Type: Float
Deadband
Travel Lo Lo Alert Point
TVL_LO_LO_ALRT_PT
77.12
RW
ALL
−
25% to 125%
−
25%
SETUP
Data Type: Float
Alert when valve position is less
than alert point. Controls DI
channels 26 & 30 regardless of
alert enable state.
Travel Lo Lo Deadband
TVL_LO_LO_DB
77.13
RW
ALL
>
= 0%,
<
= 100%
5%
SETUP
Data Type: Float
Deadband
Travel Lo Alert Point
TVL_LO_ALRT_PT
77.14
RW
ALL
−
25% to 125%
−
25%
SETUP
Data Type: Float
Alert when valve position is less
than alert point. Controls DI
channels 27 & 31 regardless of
alert enable state.
Travel Lo Deadband
TVL_LO_DB
77.15
RW
ALL
>
= 0%,
<
= 100%
5%
SETUP
Data Type: Float
Deadband
Travel Hi Alert Point
TVL_HI_ALRT_PT
77.16
RW
ALL
−
25% to 125%
125%
SETUP
Data Type: Float
Alert when valve position is less
than alert point. Controls DI
channels 28 & 32 regardless of
alert enable state.
Travel Hi Deadband
TVL_HI_DB
77.17
RW
ALL
>
= 0%,
<
= 100%
5%
SETUP
Data Type: Float
Deadband
Travel Hi Hi Alert Point
TVL_HI_HI_ALRT_PT
77.18
RW
ALL
−
25% to 125%
125%
SETUP
Data Type: Float
Alert when valve position is less
than alert point. Controls DI
channels 29 & 33 regardless of
alert enable state.
Travel Hi Hi Deadband
TVL_HI_HI_DB
77.19
RW
ALL
>
= 0%,
<
= 100%
5%
SETUP
Data Type: Float
Deadband
−
Continued
−
4
Summary of Contents for Fisher FIELDVUE DVC6000f
Page 54: ...DVC6000f Digital Valve Controllers December 2009 2 30 2 ...
Page 62: ...DVC6000f Digital Valve Controllers December 2009 4 2 4 ...
Page 127: ...Transducer Block December 2009 4 67 4 ...
Page 141: ...AO Function Block December 2009 4 81 4 ...
Page 207: ...MAI Function Block December 2009 4 147 4 ...
Page 219: ...DO Function Block December 2009 4 159 4 ...
Page 231: ...DI Function Block December 2009 4 171 4 ...
Page 302: ...DVC6000f Digital Valve Controllers December 2009 8 16 8 ...
Page 306: ...DVC6000f Digital Valve Controllers December 2009 A 4 A ...
Page 350: ...DVC6000f Digital Valve Controllers December 2009 E 6 E ...
Page 368: ...DVC6000f Digital Valve Controllers December 2009 F 18 F ...
Page 372: ...DVC6000f Digital Valve Controllers December 2009 Glossary 4 Notes G Glossary ...
Page 382: ...DVC6000f Digital Valve Controllers December 2009 Index 10 F Index ...