Transducer Block
December 2009
4-51
Table 4-13. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Description
Protect
Category
Initial Value
Range
Mode
RO /
RW
Index
Number
Advise Alarm
ADVISE_ALM
58
Data Type: DS-71
Used to report alerts to host
system
UNACKNOWLEDGED
58.1
RW
N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
NONE
ALARM_STATE
58.2
RO
N/A
0: Undefined
1: Clear
−
reported
2: Clear
−
not reported
3: Active
−
reported
4: Active
−
not reported
0=Undefined
N/A
TIME_STAMP
58.3
RO
N/A
0
N/A
SUBCODE
58.4
RO
N/A
0
N/A
VALUE
58.5
RO
N/A
0
N/A
Data Type: Float
Value of parameter at alarm time
for single alarm, 0 for multiple
alarms
Failed Active
FAILED_ACTIVE
59
RO
(1)
N/A
0: Drive Current
1: Drive Signal
2: Processor Impaired
3: Output Block Timeout
4: Blocks Set to Defaults
5: Travel Sensor
6: Outlet Pressure
Sensor
7: Supply Pressure
Sensor
8: Temperature Sensor
9: Supply Pressure
10: Temperature Limit
11: Travel Deviation
12: Travel Limit
13: Travel Accumulator
14: Cycle Counter
15: Performance Critical
16: Performance
Reduced
17: Performance
Information
18: Shutdown Alert
All bits: 0
N/A
Data Type: Bit String (4 byte)
0=inactive
1=active
Failed Alert Status
Maintenance Active
MAINT_ACTIVE
60
RO
(1)
N/A
0: Drive Current
1: Drive Signal
2: Processor Impaired
3: Output Block Timeout
4: Blocks Set to Defaults
5: Travel Sensor
6: Outlet Pressure
Sensor
7: Supply Pressure
Sensor
8: Temperature Sensor
9: Supply Pressure
10: Temperature Limit
11: Travel Deviation
12: Travel Limit
13: Travel Accumulator
14: Cycle Counter
15: Performance Critical
16: Performance
Reduced
17: Performance
Information
18: Shutdown Alert
All bits: 0
N/A
Data Type: Bit String (4 byte)
0=inactive
1=active
Maintenance Alert Status
1. These parameters can be written when PWA_SIMULATE is active and Protect Category is not ALL.
−
Continued
−
4
Summary of Contents for Fisher FIELDVUE DVC6000f
Page 54: ...DVC6000f Digital Valve Controllers December 2009 2 30 2 ...
Page 62: ...DVC6000f Digital Valve Controllers December 2009 4 2 4 ...
Page 127: ...Transducer Block December 2009 4 67 4 ...
Page 141: ...AO Function Block December 2009 4 81 4 ...
Page 207: ...MAI Function Block December 2009 4 147 4 ...
Page 219: ...DO Function Block December 2009 4 159 4 ...
Page 231: ...DI Function Block December 2009 4 171 4 ...
Page 302: ...DVC6000f Digital Valve Controllers December 2009 8 16 8 ...
Page 306: ...DVC6000f Digital Valve Controllers December 2009 A 4 A ...
Page 350: ...DVC6000f Digital Valve Controllers December 2009 E 6 E ...
Page 368: ...DVC6000f Digital Valve Controllers December 2009 F 18 F ...
Page 372: ...DVC6000f Digital Valve Controllers December 2009 Glossary 4 Notes G Glossary ...