Transducer Block
December 2009
4-43
Table 4-13. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Description
Protect
Category
Initial Value
Range
Mode
RO /
RW
Index
Number
Block Alarm
BLOCK_ALM
8
UNACKNOWLEDGED
8.1
RW
ALL
0=Undefined
1=Acknowledged
2=Unacknowledged
0
NONE
Data Type: DS-72
Used to report the BLOCK_ERR
alarm to the host system
ALARM_STATE
8.2
RO
N/A
0=Undefined
1=Clear
−
reported
2=Clear
−
not reported
3=Active
−
reported
4=Active
−
not reported
0
N/A
TIME_STAMP
8.3
RO
N/A
0
N/A
SUBCODE
8.4
RO
N/A
Subcode: Bit Number in
BLOCK_ERR
0
N/A
VALUE
8.5
RO
N/A
Value of parameter at
alarm time for a single
alarm, 0 for multiple
alarms
0
N/A
Transducer Directory
TRANSDUCER_DIRECTORY
9
RO
N/A
1,1
1,1
N/A
Data Type: Array [2] of Unit16
Not used
Transducer Type
TRANSDUCER_TYPE
10
RO
106
106
N/A
Data Type: Uint16
Identifies the type of the transducer.
Transducer Error
XD_ERROR or TDC_ERROR
11
RO
Valid Numbers: 0 = No
Error
0
N/A
Data Type: Uint8
Error code for the transducer block.
Collection Directory
COLLECTION_DIRECTORY
12
RO
1,1,1,1,1
1,1,1,1,1
N/A
Data Type: Array [5] of Unit32
Not used
FINAL_VALUE
13
Setpoint Status
STATUS
13.1
RW
MAN
OOS
N/A
NONE
Data Type: DS-65
In Travel Control: Setpoint for valve
travel in %, prior to
characterization.
In Pressure Control: Setpoint for
implied valve travel as % or
pressure range, prior to
characterization.
FINAL_VALUE is not updated
unless the AO block is selected in
FEATURE_SELECT. For example,
FINAL_VALUE still has last value
written by AO channel 1 when DO
is in control.
Setpoint
VALUE
13.2
RW
MAN
OOS
−
25 to 125
N/A
NONE
Setpoint Range
FINAL_VALUE_RANGE
14
Data Type: DS-68
High and Low range limit values,
engineering units code, and
number of digits to the right of the
decimal place to be used to display
the Final Value.
EU_100
14.1
RO
N/A
100
100
N/A
EU_0
14.2
RO
N/A
0
0
N/A
UNITS_INDEX
14.3
RO
N/A
PERCENT
1342
N/A
DECIMAL
14.4
RO
N/A
2
2
N/A
Travel Cutoff Hi
FINAL_VALUE_CUTOFF_HI
15
RW
MAN
OOS
−
25 to 125
99.5
SETUP
Data Type: Float
When the servo goes above this %
of span, the stem position goes to
the upper limit. Cutoffs are OFF
when Low is at
−
25% and high is at
+125%. Must be
>
low
.625%.
Travel Cutoff Lo
FINAL_VALUE_CUTOFF_LO
16
RW
MAN
OOS
−
25 to 125
0.5
SETUP
Data Type: Float
When the servo goes below this %
of span, the stem position goes to
the lower limit. Cutoffs are OFF
when Low is at
−
25% and high is at
+125%. Must be
<
hi cutoff
−
.625%.
−
Continued
−
4
Summary of Contents for Fisher FIELDVUE DVC6000f
Page 54: ...DVC6000f Digital Valve Controllers December 2009 2 30 2 ...
Page 62: ...DVC6000f Digital Valve Controllers December 2009 4 2 4 ...
Page 127: ...Transducer Block December 2009 4 67 4 ...
Page 141: ...AO Function Block December 2009 4 81 4 ...
Page 207: ...MAI Function Block December 2009 4 147 4 ...
Page 219: ...DO Function Block December 2009 4 159 4 ...
Page 231: ...DI Function Block December 2009 4 171 4 ...
Page 302: ...DVC6000f Digital Valve Controllers December 2009 8 16 8 ...
Page 306: ...DVC6000f Digital Valve Controllers December 2009 A 4 A ...
Page 350: ...DVC6000f Digital Valve Controllers December 2009 E 6 E ...
Page 368: ...DVC6000f Digital Valve Controllers December 2009 F 18 F ...
Page 372: ...DVC6000f Digital Valve Controllers December 2009 Glossary 4 Notes G Glossary ...
Page 382: ...DVC6000f Digital Valve Controllers December 2009 Index 10 F Index ...