Viewing Device Variables and Diagnostics
September 2013
6-3
seconds. If this alert is indicated, check the instrument
supply pressure. If the failure persists, ensure the
printed wiring board assembly is properly mounted
onto the Module Base Assembly, and the pressure
sensor O-rings are properly installed. If the alert does
not clear after restarting the instrument, replace the
printed wiring board assembly.
Note
The pressure sensor alert is used for
output A, output B, and the supply
pressure sensor. Check the pressure
values to see which sensor is causing
the alert.
Temperature Sensor
Temperature Sensor Alert—This alert is indicated
when the instrument temperature sensor fails, or the
sensor reading is outside of the range of
−
40 to 85
C
(
−
40 to 185
F). The temperature reading is used
internally for temperature compensation of inputs. If
this alert is indicated, restart the instrument and see if
it clears. If it does not clear, replace the printed wiring
board assembly.
Environment— If an environment alert is active
it will appear under ENVIRO ALERTS.
Supply Pressure
Supply Pressure Lo Alert—This alert is indicated
when supply pressure is lower than the configured
limit.
Auxiliary Terminal Alert
Aux Terminal Alert—This alert is set when the
auxiliary input terminals are either open or closed,
depending upon the selection for the Auxiliary Input
Alert State.
Loop Current Validation Alert— This alert is
activated if the loop current is out of valid range. If the
control system is known to output currents outside of
this range, the loop current shutdown should not be
enabled. If this alert is indicated, clear the alert by
restarting the instrument with the loop current verified
to be in the valid range. If the alert does not clear,
replace the printed wiring board. Only available in
firmware 9, 10, and 11.
Travel— If a travel alert is active it will appear
under TRAVEL ALERTS.
Table 6-1. Alerts Included in Alert Groups for Alert Record
Alert Group
Alerts Include in Group
Valve Alerts
Travel Alert Lo
Travel Alert Hi
Travel Alert Lo Lo
Travel Alert Hi Hi
Travel deviation
Drive signal
Failure Alerts
No free time
Flash ROM fail
Drive current fail
Ref Voltage fail
NVM fail
Temperature sensor fail
Pressure sensor fail
Travel sensor fail
Miscellaneous Alerts
Auxiliary input
Travel Deviation
Travel Deviation Alert—The difference between
Setpoint and Travel is greater than the configured
limits.
Travel Limit
Travel Alert Hi Hi—This alert is indicated if the
Travel is greater than the configured limit.
Travel Alert Lo Lo—This alert is indicated if the
Travel is lower than the configured limit.
Travel Limit Hi/Lo
Travel Alert Hi—This alert is indicated if the Travel
is greater than the configured limit.
Travel Alert Lo—This alert is indicated if the Travel
is lower than the configured limit.
Travel Limit / Cutoff
Travel Limit/Cutoff Hi—This alert is indicated if the
Travel is limited high or the high cutoff is in effect.
Travel Limit/Cutoff Lo—This alert is indicated if the
Travel is limited low or the low cutoff is in effect.
Travel History— If a travel history alert is active
it will appear under TVL HIST ALERTS.
Cycle Count
Cycle Count Alert—This alert is indicated if the
Cycle Counter exceeds the Cycle Count Alert Point.
Travel Accumulator
Travel Accumulator Alert—This alert is indicated if
the Travel Accumulator exceeds the Travel
Accumulator Alert Point.
SIS (ODV tier only)— If an SIS alert is active it
will appear under SIS ALERTS.
Partial Stroke Test (PST)
Valve Stuck or Pressure/Travel Path
Obstructed—This alert is indicated if the valve is stuck
or the pressure/travel path is obstructed.
End Point Pressure Deviation
Pressure Deviation Alert—The alert is indicated if
6
Summary of Contents for Fisher FIELDVUE DVC6000
Page 2: ......
Page 22: ...DVC6000 Digital Valve Controllers September 2013 1 12 1 ...
Page 82: ...DVC6000 Digital Valve Controllers September 2013 4 22 4 ...
Page 94: ...DVC6000 Digital Valve Controllers September 2013 5 12 5 ...
Page 139: ...Loop Schematics Nameplates September 2013 B 1 B B Appendix B Loop Schematics Nameplates B ...
Page 161: ......