Instruction Manual
D102748X012
DLC3010 Digital Level Controller
Configuration
May 2018
55
24
22
20
18
16
14
12
10
8
6
4
2
PV (m)
DEVICE OUTPUT (mA)
-2 0 2 4 6 8 10 12
PV LOLO ALERT ENABLED
LOLO THRESHOLD: 2 m
ALARM SETTING: HIGH
OUTPUT ACTION: REVERSE
RANGE: 10 TO 0 m
Figure 4‐9. PV LoLo Alerts
24
22
20
18
16
14
12
10
8
6
4
2
-2 0 2 4 6 8 10 12
PV (m)
DEVICE OUTPUT (mA)
PV (m)
PV (m)
DEVICE OUTPUT (mA)
DEVICE OUTPUT (mA)
PV LOLO ALERT ENABLED
LOLO THRESHOLD: 2 m
ALARM SETTING: LOW
OUTPUT ACTION: DIRECT
RANGE: 0 TO 10 m
PV LOLO ALERT ENABLED
LOLO THRESHOLD: 2 m
ALARM SETTING: LOW
OUTPUT ACTION: REVERSE
RANGE: 10 TO 0 m
NAMUR NE 43 LOW ALARM LEVEL
24
22
20
18
16
14
12
10
8
6
4
2
-2 0 2 4 6 8 10 12
24
22
20
18
16
14
12
10
8
6
4
2
-2 0 2 4 6 8 10 12
NAMUR NE 43 HIGH ALARM LEVEL
NAMUR NE 43 HIGH ALARM LEVEL
PV LOLO ALERT ENABLED
LOLO THRESHOLD: 2 m
ALARM SETTING: HIGH
OUTPUT ACTION: DIRECT
RANGE: 0 TO 10 m
NAMUR NE 43 LOW ALARM LEVEL
PLOT A
PLOT B
PLOT C
PLOT D
1
NOTE THAT THE LOW ALARM CURRENT CAPABILITY IS NOT NAMUR NE 43 COMPLIANT.
1
1
D
PV Value
is the current process variable (level, interface, or density) in engineering units.
D
Upper Range Value
is the highest value of the primary variable that the digital level controller is currently configured
to measure in the 4 to 20 mA loop.