Instruction Manual

D104734X012

ATST Desuperheater

July 2022

3

Figure 2. Typical Fisher ATST Installation

KEY:
DSPL = DOWNSTREAM STRAIGHT PIPE LENGTH
PI = PROPORTIONAL INTEGRAL CONTROLLER
PSL = PRESSURE SENSOR LENGTH
PT = PRESSURE TRANSMITTER
TE = TEMPERATURE SENSOR ELEMENT
TSL = TEMPERATURE SENSOR LENGTH
USPL = UPSTREAM STRAIGHT PIPE LENGTH

USPL

X0355A-1

TSL

PSL

DSPL

PI

PT

TE

Installation

  WARNING

Always wear protective gloves, clothing, and eyewear when performing any installation operations to avoid personal
injury.

Personal injury or equipment damage caused by sudden release of pressure may result if the ATST desuperheater is
installed where service conditions could exceed the limits of the pressure rating noted on the nameplate. To avoid such
injury or damage, provide a relief valve for over pressure protection as required by government or accepted industry codes
and good engineering practices.

Check with your process or safety engineer for any additional measures that must be taken to protect against process
media.

If installing into an existing application, also refer to the WARNING at the beginning of the Maintenance section in this
instruction manual.

  WARNING

When ordered, the desuperheater configuration and construction materials were selected to meet particular pressure,
temperature, pressure drop, and fluid conditions. Do not apply any other conditions to the desuperheater without first
contacting your 

Emerson sales office

.

1.  Before installation, all piping upstream of the desuperheater must be cleaned so that no loose materials such as

welding slag, dirt or other foreign matter are left in the pipe. Use care to keep foreign matter out of the line
openings while preparing the desuperheater installation.

Summary of Contents for Fisher ATST Desuperheater

Page 1: ...nual including all safety cautions and warnings If you have any questions about these instructions contact your Emerson sales office before proceeding Description Water atomization and vaporization are key elements in any steam conditioning application The ATST design incorporates a manifold of patented nozzles to inject atomizing steam and spraywater into process steam These specialized nozzles p...

Page 2: ... Inlet Pressures 1 Consistent with applicable pressure temperature ratings per ASME B16 34 Maximum Unit Cv for Spraywater Flow Contact your Emerson sales office Spraywater Pressure Required 2 3 5 to 35 bar 50 to 500 psi greater than steam line pressure Atomizing Steam Pressure Required Atomizing steam source pressure typically should be at least 2 times the pressure of the steam to be desuperheate...

Page 3: ...provide a relief valve for over pressure protection as required by government or accepted industry codes and good engineering practices Check with your process or safety engineer for any additional measures that must be taken to protect against process media If installing into an existing application also refer to the WARNING at the beginning of the Maintenance section in this instruction manual W...

Page 4: ...he piping 2 Arrange lifting slings or other lifting and rigging equipment appropriate for the desuperheater weight and configuration around the main steam pipe to safely lift the ATST to the pipe opening WARNING Do not expose the ATST to undue stresses by installing it in bent pipes or flanges Personal injury and equipment damage could result from flange sealing failure due to improper installatio...

Page 5: ...ture and a temperature transmitter TT transmits the signal to the temperature control device The output signal from the controller is sent to the positioner on the cooling water spraywater control valve SWCV The positioner s output signal strokes the SWCV open increasing water pressure on the nozzles Increasing water pressure upstream of the nozzles increases water flow through the nozzles The ato...

Page 6: ... erosion thermal fatigue and other damage Consult your local Emerson Service Center or Emerson Accredited Service Provider for a recommendation on necessary weld repair or replacement Nozzle Maintenance and Replacement When subjected to normal operating conditions it is possible that wear blockage and or fatigue will occur to the nozzle assembly During regularly scheduled maintenance visually insp...

Page 7: ...e Alignment Pin Location GH01927 PIN 5 Reassemble in the following order nozzle gasket key 9 nozzle body flange gasket key 8 spray nozzle key 10 second nozzle gasket key 9 nozzle alignment pin key 3 nozzle body flange assembly key 7 washers key 4 and stud nuts key 6 Ensure the nozzle is installed such that the flow arrow is aligned with the direction of process steam flow It is recommended that an...

Page 8: ...t supplied by Emerson should not under any circumstances be used in any Fisher desuperheater because they may void your warranty might adversely affect the performance of the desuperheater and could cause personal injury and property damage Parts List Note Contact your Emerson sales office for Part Ordering information Key Description 1 Steam Pipe 2 Nozzle Body 3 Nozzle Alignment Pin 4 Nozzle Body...

Page 9: ...Instruction Manual D104734X012 ATST Desuperheater July 2022 9 Figure 5 Fisher ATST Desuperheater FLOW ...

Page 10: ...Instruction Manual D104734X012 ATST Desuperheater July 2022 10 Figure 6 Fisher ATST Desuperheater Alternate View ...

Page 11: ...Instruction Manual D104734X012 ATST Desuperheater July 2022 11 ...

Page 12: ...s which are available upon request We reserve the right to modify or improve the designs or specifications of such products at any time without notice E 2022 Fisher Controls International LLC All rights reserved Fisher is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co Emerson Automation Solutions Emerson and the Emerson logo are tradem...

Reviews: