Types 627W and 627WH

Installation Guide

D102504X014
English - March 2009

Introduction

This installation guide provides instructions for 

installation, startup and adjustment. To receive a 

copy of the instruction manual, contact your local 

Sales Office or view a copy at www.fisher.com. For 

further information refer to: Types 672W and 627WH 

Instruction Manual, D102504X012.

PED Category

This product may be used as a safety accessory 

with pressure equipment in the following Pressure 

Equipment Directive categories. It may also be used 

outside of the Pressure Equipment Directive using 

sound engineering practice (SEP) per table below. 

For information on the current PED revision see 

Bulletin: 

D103053X012

PRODUCT SIZE

CATEGORIES

DN 20 and 25 / NPS 3/4 and 1

SEP

DN 50 / NPS 2

II

Specifications

Available Constructions

Type 627W:

 Direct operated pressure reducing 

liquid regulator.

Type 627WH:

 Type 627W with a diaphragm limiter 

to deliver a higher outlet pressure.

Control Line Option:

 Type 627W or 627WH with 

a stem seal between the body outlet pressure and 

diaphragm case. Pressure is measured under 

the diaphragm through the 1/4 NPT downstream 

control line connection.

Body Sizes and End Connection Styles 

NPT:

 DN 20, 25 or 50 / NPS 3/4, 1 or 2 

CL150, CL300, CL600 RF Flanged:

 

DN 25 or 50 / NPS 1 or 2 

PN 16/25/40:

 DN 25 or 50 / NPS 1 or 2

Maximum Spring and Diaphragm 

Casing Pressure

(1)

See Table 1

Body Pressure Shell Rating

(1)

NPT (Steel):

 138 bar / 2000 psig

NPT (Ductile Iron):

 68.9 bar / 1000 psig 

CL600 RF Flanged (Steel):

 103 bar / 1500 psig

Maximum Operating Inlet and Outlet 

Pressure Ranges

(1)

See Table 2 for pressures by orifice and spring range

Outlet Pressure Ranges

See Table 2

Orifice Diameters

Standard:

 6.4 or 13 mm / 1/4 or 1/2 in.

Optional:

 2.4, 3.2, 4.8 or 9.5 mm / 

3/32, 1/8, 3/16 or 3/8 in.

Proof Test Pressure

All Pressure Retaining Components have been

proof-tested per Directive.

Temperature Capabilities

(1)(2)

Nitrile (NBR):

 -40 to 82°C / -40 to 180°F

Fluorocarbon (FKM):

 -18 to 149°C / 0 to 300°F

Ethylenepropylene (EPDM):

 -40 to 135°C / 

-40 to 275°F

Perfluoroelastomer (FFKM):

 -18 to 204°C / 

0 to 400°F

Nylon (PA):

 -40 to 93°C / -40 to 200°F

Polytetrafluoroethylene (PTFE):

 -40 to 204°C / 

-40 to 400°F

Installation

!

WARNING

Only qualified personnel should install 

or service a regulator. Regulators should 

be installed, operated and maintained 

in accordance with international and 

applicable codes and regulations and 

Emerson Process Management Regulator 

Technologies, Inc. instructions.
If the regulator vents fluid or a leak 

develops in the system, it indicates that 

service is required. Failure to take the 

regulator out of service immediately may 

create a hazardous condition.
Personal injury, equipment damage or 

leakage due to escaping fluid or bursting 

of pressure containing parts may result 

if this regulator is overpressured or 

is installed where service conditions 

could exceed the limits given in the 

Specifications section or where conditions 

exceed any ratings of the adjacent piping 

or piping connections.

1. The pressure/temperature limits in this installation guide and any applicable standard or code limitation should not be exceeded.

2. Stainless steel body is rated to -40°C / -40°F. Steel and ductile iron bodies are rated to -29°C / -20°F.

Summary of Contents for FISHER 627W

Page 1: ... 103 bar 1500 psig Maximum Operating Inlet and Outlet Pressure Ranges 1 See Table 2 for pressures by orifice and spring range Outlet Pressure Ranges See Table 2 Orifice Diameters Standard 6 4 or 13 mm 1 4 or 1 2 in Optional 2 4 3 2 4 8 or 9 5 mm 3 32 1 8 3 16 or 3 8 in Proof Test Pressure All Pressure Retaining Components have been proof tested per Directive Temperature Capabilities 1 2 Nitrile NB...

Page 2: ...ter than the safe working pressure of the downstream equipment Regulator operation below the maximum pressure limitations does not preclude the possibility of damage from external sources or debris in the line The regulator should be inspected for damage after any overpressure condition Startup The regulator is factory set at approximately the midpoint of the spring range or the pressure requested...

Page 3: ...d Outlet Pressure Ranges TYPE OUTLET PRESSURE RANGE AND COLOR bar psig ORIFICE SIZE MAXIMUM INLET PRESSURE MAXIMUM DIFFERENTIAL PRESSURE Elastomer Disk Nylon Disk Elastomer Disk Nylon Disk mm In bar psig bar psig bar psig bar psig 627W 0 69 to 1 4 10 to 20 Yellow 6 4 1 4 15 2 220 29 0 420 13 8 200 27 6 400 13 1 2 15 2 220 17 2 250 13 8 200 17 2 250 1 0 to 2 8 15 to 40 Green 6 4 1 4 16 5 240 30 3 4...

Page 4: ...are the property of their prospective owners Fisher is a mark owned by Fisher Controls International LLC a business of Emerson Automation Solutions The contents of this publication are presented for information purposes only and while effort has been made to ensure their accuracy they are not to be construed as warranties or guarantees express or implied regarding the products or services describe...

Reviews: