
Instruction Manual
D200354X012
4200 Transmitters
March 2011
3
Table 1. Specifications
Available Configurations
Input Signal
Source: Single potentiometer is standard or a dual
potentiometer is available for the 4215 only. Refer to
table 3 for zero and span limits
Output Signal
Range:
4 to 20 milliampere DC transmitter output
(4210, 4211, 4215, 4220, and 4221 transmitters)
Load Impedance (transmitter only):
Output Current Limit:
30 milliamperes DC maximum
Switches:
ON/OFF condition of high and low position
switch relay (SPDT)
Power Supply Requirements
Transmitter Terminal
Voltage (VDC)
Current
1
Required
(mA)
Min
Max
Transmitter Only
11
30
20 max.
Position Switch with
Transmitter
20
30
80 max.
Position Switch without
Transmitter
20
30
50 max.
1. Values indicate minimum power supply capabilities.
Recommended Power Supply
24 volts DC nominal
Position Switch Relays
Type:
Two single‐pole, double‐throw relays (SPDT)
Service Rating:
The relay contact rating is 5 amperes
at either 30 volts DC or 120 volts AC (resistive load)
Life Expectancy:
100,000 operations at rated load, or
50,000 operations at a typical inrush current of 10
amperes with 120 volts AC lamp or motor load
Reference Accuracy
±
1% of output span. Includes combined effects of
hysteresis, linearity, and deadband
Repeatability
±
0.25% of span
Operating Influences
Ambient Temperature:
For a 56
_
C (100
_
F) change in
normal operating conditions, maximum zero shift is
±
0.5%; maximum span shift is
±
0.75% of span
Power Supply:
Output signal changes less than
±
0.1%
when operating terminal voltage varies between 11
and 30 volts DC
Electromagnetic Compatibility for 4211 and 4221:
Meets EN 61326‐1 (First Edition)
Immunity—Industrial locations per Table 2 of
the EN 61326‐1 standard. Performance is
shown in table 4 below.
Emissions—Class A
ISM equipment rating: Group 1, Class A
Operating Conditions
Condition
Normal and
Operative
Limits
Transportation
and Storage
Limits
Normal
Reference
Ambient
Temperature
-40 to 71
_
C
(-40 to 160
_
F)
-50 to 80
_
C (-60
to 180
_
F)
25
_
C
(77
_
F)
Ambient
Relative
Humidity
10 to 95%
10 to 95%
40%
Mounting
The instrument can be mounted on the actuator of
sliding‐stem or rotary valves or on other devices
Electrical Classification
CSA—
Intrinsically Safe, Explosion-proof,
Dust Ignition-proof
FM—
Intrinsically Safe, Explosion‐proof,
Dust Ignition-proof, Non‐Incendive
ATEX
—Intrinsically Safe, Type n, Dust
Refer to Special Instructions for “Safe Use” and
Installations in Hazardous Locations in the Installation
section, tables 5, 6, and 7, and figures 24, 25, 26,
and 27.
Housing
NEMA 4X; CSA Enclosure 4X; IP66
Approximate Weight
Transmitter Without Mounting Bracket: 1.8 kg
(4 pounds)
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 - Process Instrument Terminology.