DVC6200f Digital Valve Controller
November 2010
194
DI Function Block Parameter List
Read/Write Capability: RO
−
Read Only, RW
−
Read Write
Mode: The block mode(s) required to write to the parameter
Double indentation and shaded Index Number indicates sub-parameter
Table 4-81. Discrete Input Function Block Parameter Definitions
Label
PARAMETER_NAME
Index
Number
RO /
RW
Block
Mode
Range
Initial Value
Description
Static Revision
ST_REV
1
RO
N/A
0 to 65535
0
Data Type: Unsigned16
The revision level of the static data
associated with the function block. The
revision value will be incremented each time
a static parameter value in the block is
changed.
Tag Description
TAG_DESC
2
RW
ALL
7 bit ASCII
Spaces
Data Type: Octet String
The user description of the intended
application of the block.
Strategy
STRATEGY
3
RW
ALL
0 to 65535
0
Data Type: Unsigned16
The strategy field can be used to identify
grouping of blocks. This data is not checked
or processed by the block.
Alert Key
ALERT_KEY
4
RW
ALL
1 to 255
0
Data Type: Unsigned8
The identification number of the plant unit.
This information may be used in the host for
sorting alarms, etc.
Block Mode
MODE_BLK
5
Data Type: DS-69
Valid Bits: 7:OOS, 4:MAN, 3:AUTO
The actual, target, permitted, and normal
modes of the block.
Target: The requested block mode
Actual: The current mode of the block
Permitted: Allowed modes for Target
Normal: Most common mode for Target
TARGET
5.1
RW
ALL
OOS
MAN
AUTO
OOS until
block is
configured,
then last valid
target
ACTUAL
5.2
RO
ALL
OOS
PERMITTED
5.3
RW
ALL
OOS+MAN+AUTO
OOS+MAN+
AUTO
NORMAL
5.4
RO
ALL
AUTO
Block Error
BLOCK_ERR
6
RO
N/A
Defined Bits
1: Block Configuration
Error
3: Simulate Active
7: Input Failure / Bad PV
Status
14: Power-up
15: Out-of-Service
Dynamic
Data Type: Bit String
0=Inactive
1=Active
This parameter reflects the error status
associated with the hardware or software
components associated with a block. Multiple
errors may be shown, see table 4-80.
Process Value Discrete
PV_D
7
RO
N/A
PV_D Status set equal to
Field_Val_D Status
Dynamic
Data Type: DS-66
The process variable used in block
execution. Value is converted from
Readback to show the actuator position in
the same units as the set point value.
Output Discrete
OUT_D
8
OOS
MAN
OUT_STATE
Data Type: DS-66
The primary discrete value calculated as a
result of executing the function.
Simulate Discrete
SIMULATE_D
9
Data Type: DS-83
Allows the transducer discrete input or output
to the block to be manually supplied when
simulate is enabled. When simulation is
disabled, the simulate value and status track
the actual value and status.
SIMULATE_STATUS
9.1
ALL
0
SIMULATE_VALUE
9.2
ALL
0
TRANSDUCER_STATUS
9.3
RO
ALL
0
TRANSDUCER_VALUE
9.4
RO
ALL
0
ENABLE/DISABLE
9.5
0=Not initialized
1=Simulation Disabled
2=Simulation Active
1=Simulation
Disabled
−
Continued
−
4
Summary of Contents for FIELDVUE DVC6200f
Page 42: ...DVC6200f Digital Valve Controller November 2010 30 4 ...
Page 60: ...DVC6200f Digital Valve Controller November 2010 48 4 ...
Page 108: ...DVC6200f Digital Valve Controller November 2010 96 4 ...
Page 122: ...DVC6200f Digital Valve Controller November 2010 110 4 ...
Page 188: ...DVC6200f Digital Valve Controller November 2010 176 4 ...
Page 200: ...DVC6200f Digital Valve Controller November 2010 188 4 ...
Page 216: ...DVC6200f Digital Valve Controller November 2010 204 5 ...
Page 250: ...DVC6200f Digital Valve Controller November 2010 238 8 ...
Page 254: ...DVC6200f Digital Valve Controller November 2010 242 A ...
Page 284: ...DVC6200f Digital Valve Controller November 2010 272 D ...
Page 290: ...DVC6200f Digital Valve Controller November 2010 278 E ...
Page 308: ...DVC6200f Digital Valve Controller November 2010 296 F ...
Page 312: ...DVC6200f Digital Valve Controller September 2010 300 Notes G Glossary ...
Page 324: ...DVC6200f Digital Valve Controller November 2010 312 F Index ...