AI Function Block
November 2010
159
Table 4-54. Channel Selections for the Analog Input Function Block
Channel
Parameter
(1)
Block
Index
Number
XD_SCALE Units
2
TRAVEL_TARGET
TB
49
% (1342)
3
FINAL_POSITION_VALUE
TB
17
% (1342)
4
TRAVEL
TB
34
% (1342)
5
SUPPLY_PRESS
TB
35
psig (1143), bar (1137), kPa (1133), inHg (1155), inH20 (1146), kg/cm2 (1145)
6
PRESSURE_A
TB
36
psig (1143), bar (1137), kPa (1133), inHg (1155), inH20 (1146), kg/cm2 (1145)
7
PRESSURE_B
TB
37
psig (1143), bar (1137), kPa (1133), inHg (1155), inH20 (1146), kg/cm2 (1145)
8
PRESSURE_DIFF
TB
38
psig (1143), bar (1137), kPa (1133), inHg (1155), inH20 (1146), kg/cm2 (1145)
9
DRIVE_SIGNAL
TB
53
% (1342)
10
TRAVEL_DEVIATION
TB
52
% (1342)
11
TEMPERATURE
TB
48
C (1001),
F (1002)
12
CYCLE_COUNT
TB
73
no units (1588)
13
TRAVEL_ACCUMULATION
TB
72
% (1342)
1. Refer to table 4-14 for transducer block parameter descriptions and table 4-25 for AO parameter descriptions.
Status Handling
The AI block only gets Good Non-Specified Unlimited
or Bad Device Failure for status from the transducer.
This is reflected in FIELD_VAL.STATUS [19.1].
PV.STATUS [7.1] is the same as
FIELD_VAL.STATUS [19.1]. OUT.STATUS [8.1] can
also reflect Bad, Out of Service in addition to
PV.STATUS [7.1] values.
In the STATUS_OPTS [14] parameter, you can select
from the following options to control the status
handling:
Propagate Fail Forward—If the status from the
sensor is Bad, Device failure or Bad, Sensor failure,
propogate it to OUT without generating an alarm. The
use of these sub-status in OUT is determined by this
option. Through this option, you may determine
whether alarming (sending out an alert) will be done by
the block or propagated downstream for alarming.
OUT (mode in man)
OUT (mode in auto)
PV
63% of Change
TIME (seconds)
FIELD_VAL
PV_FTIME
FIELDBUS-FBUS_03A
Figure 4-23. Analog Input Function Block Timing Diagram
4
Summary of Contents for FIELDVUE DVC6200f
Page 42: ...DVC6200f Digital Valve Controller November 2010 30 4 ...
Page 60: ...DVC6200f Digital Valve Controller November 2010 48 4 ...
Page 108: ...DVC6200f Digital Valve Controller November 2010 96 4 ...
Page 122: ...DVC6200f Digital Valve Controller November 2010 110 4 ...
Page 188: ...DVC6200f Digital Valve Controller November 2010 176 4 ...
Page 200: ...DVC6200f Digital Valve Controller November 2010 188 4 ...
Page 216: ...DVC6200f Digital Valve Controller November 2010 204 5 ...
Page 250: ...DVC6200f Digital Valve Controller November 2010 238 8 ...
Page 254: ...DVC6200f Digital Valve Controller November 2010 242 A ...
Page 284: ...DVC6200f Digital Valve Controller November 2010 272 D ...
Page 290: ...DVC6200f Digital Valve Controller November 2010 278 E ...
Page 308: ...DVC6200f Digital Valve Controller November 2010 296 F ...
Page 312: ...DVC6200f Digital Valve Controller September 2010 300 Notes G Glossary ...
Page 324: ...DVC6200f Digital Valve Controller November 2010 312 F Index ...