background image

F02/EPI2 Quarter-Turn 

Electric Actuator

Base and OM1 Card

 

F02/EPI2 Base and OM1 Card 

April 2018

Quick Start Guide

VCIOM-08536-US Rev. 0

Base Card

 

F02/EPI2 Quarter-Turn Electric Actuator

Figure 1 

Model 063-125

Green LED 
Power ON

Dip switch 

SW3

Push button

SW5

Red LED
Enter configuration

Rotary switch

SW4

Rotary switch

SW6

Figure 2 

Model 250-500-1000-2000

Dip switch

SW3

Green LED
Power ON

Rotary switch

SW6

Rotary switch

SW4

Red LED
Enter configuration

Push button

SW5

Table 1.

Operating Times

Model

Nominal torque

(Nm/lb.in.)

Operating time (secs 90

o

) at selected step

8

6

4

063

63/600

15

28

48

125

125/1300

15

28

48

250

250/2500

15

28

48

500

500/5100

15

28

48

1000

1000/9100

24

45

80

2000

2000/17700

53

100

180

Note:

(*) Factory

PRE-INSTALLATION:

 See 

VCIOM-2881

 INSTALLATION AND MAINTENANCE INSTRUCTIONS. Not performing the following procedures will invalidate the product warranty.

INSTALLATION: 

To assemble the actuator onto the valve proceed as follows:

a.  Verify proper mounting hardware. 
b.  Verify proper electrical service to the actuator 
c. 

Lubricate the valve stem with oil or grease to make the assembly easier: pay attention not to contaminate with lubricant the flange surfaces which transmit the actuator torque.

d. 

Clean the valve flange and remove anything that might prevent a perfect adherence to the actuator flange and especially all traces of grease. 

e.  Install the actuator onto the valve so that the shaft out put drive enters the groove of the stem extension. This coupling must take place without forcing and only with the weight of the 
actuator. 
f. 

Ensure actuator and valve are in same orientation when bolting together. 

g.  With the handwheel, operate the actuator to verify it moves the valve smoothly.

 WARNING 

The configuration must be done while the actuator is powered on. As a consequence, all configuration operations must be carried out by specifically qualified personnel for operations on 

 

powered electronic cards. Hazardous voltages may be present. Before connecting power to the actuator, check that the voltages are correct and according to the nameplate data. Improper power 

supply will cause permanent damage to the electrical components. Actuator configuration programming requires removal of the actuator cover. Refer to VCIOM-2881 IOM for instructions.

Quick Start Guide 

VCIOM-08536-US Rev. 0

F02/EPI2 Base and OM1 Card

April 2018

See 

table 1

Rotary Switch Settings

Configurations

Move switch 

SW4

 to position 

indicated in each row

Move switch 

SW6

 to position 

indicated in each row 

SW3

Confirm by 

SW5

Red 

LED

SW3

CLOSE LIMIT by position

2

1 (*)

En

te

r s

et u

p c

onfigur

ati

on m

ovin

g S

W3 t

o O

N

PUS

H

LED lights up once

Exit s

et u

p c

onfigur

ati

on m

ovin

g S

W3 t

o 1 (R

un Se

ttin

g)

Drive the actuator to 
the CLOSE position 
using the handwheel

0

0

OPEN LIMIT by position

3

1 (*)

LED lights up once

Drive the actuator to 
the OPEN position 
using the handwheel

1

0

CLOSE LIMIT by torque

2

0 (*)

Operate the 
actuator to direction 
bylocal/remote 
control and wait 
until it stops by 

torque

OPEN LIMIT by torque

3

0 (*)

CLOSING speed

4

4

6 (*)

8

LED lights up once

OPENING speed

5

% CLOSING torque

6

= 50%

= 75%

9 = 100% (*)

% OPENING torque

7

CW/CCW

8

0 = CW (*)

= CCW

BLINKER/local selector

4

0 = off (*)

= Blinker

= Loc. Sel.

Reviews: