14.2
Analog Outputs
The Unidrive SP has two Analog Outputs that can be configured to represent any base drive parameter (00.00 - 21.51). The default
configuration for the two drive analog outputs are Speed Feedback (3.02) and Active Current (4.02). Using this method will
automatically update the analog output value.
To configure the drive Analog Output to represent an SM-EZMotion module parameter, the Analog Output Source of the drive (7.19
or 7.22) must be set to a drive parameter in Menu 20 (20.21 through 20.40). Menu 20 parameters 21 through 40 must be used
because they are 32-bit parameters. Once the Analog Output Source has been set to a 32-bit parameter, the SM-EZMotion user
program must be coded to write the value of the desired SM-EZMotion parameter to the 32-bit menu parameter. Below is an
example of this process.
158
Y
File Corruption Error - Consult
Factory
159
Y
File Corruption Error - Consult
Factory
160
Y
File Corruption Error - Consult
Factory
161
Y
File Corruption Error - Consult
Factory
162
Y
File Corruption Error - Consult
Factory
163
Y
File Corruption Error - Consult
Factory
164
Y
File Corruption Error - Consult
Factory
165
Y
File Corruption Error - Consult
Factory
166
Y
Program Error - EZMotion
Parameter Write Out of Range
Value written to SM-EZMotion
parameter in user program is out
of range
171
Y
Invalid Slot 1 Selection
Option module selected for Slot 1
in PowerTools Pro file does not
match actual module type fitted
Switch module located in Slot 1 to
match module type selected in
PowerTools Pro file. Alternatively,
update the PowerTools Pro
configuration to match the module
type actually fitted, and then re-
download the configuration.
172
Y
Invalid Slot 2 Selection
Option module selected for Slot 2
in PowerTools Pro file does not
match actual module type fitted
Switch module located in Slot 2 to
match module type selected in
PowerTools Pro file. Alternatively,
update the PowerTools Pro
configuration to match the module
type actually fitted, and then re-
download the configuration.
173
Y
Invalid Slot 3 Selection
Option module selected for Slot 3
in PowerTools Pro file does not
match actual module type fitted
Switch module located in Slot 3 to
match module type selected in
PowerTools Pro file. Alternatively,
update the PowerTools Pro
configuration to match the module
type actually fitted, and then re-
download the configuration.
174
Y
File Corruption Error - Consult
Factory
175
Y
Module Output Overload
EZMotion can only supply 20mA
maximum total output current. If
this fault occurs, the digital output
device attached to the module
outputs is drawing too much
current.
Modify circuitry of devices
connected to the EZMotion digital
outputs so that they draw no more
than 20mA total.
Error
Code
(x.50)
Cause
Trip?
Error
Possible Reason
Possible Solution
Summary of Contents for EZMotion
Page 2: ......
Page 12: ...x EZMotion User Programming Guide www controltechniques com Revision A8 ...
Page 18: ...6 EZMotion User Programming Guide www controltechniques com Revision A8 ...
Page 36: ...24 EZMotion User Programming Guide www controltechniques com Revision A8 ...
Page 158: ...146 EZMotion User Programming Guide www controltechniques com Revision A8 ...
Page 186: ...174 EZMotion User Programming Guide www controltechniques com Revision A8 ...
Page 266: ...256 EZMotion User Programming Guide www controltechniques com Revision A8 ...
Page 267: ......