Clamp Install:
For screw torques and wire stripping by frame please see the picture below.
Circuit Breaker Sizing
The circuit breaker selected must be in accordance with the National Electric Code (NEC) Requirements. The
NEC determines that circuit breakers should handle 80% of their rated capacity for continuous loads and 100%
for intermittent loads. NEC Articles 210.20, 215.3, and 430 address the NEC requirements in more detail. For
safety reasons it is recommended to assume all loads are continuous.
To explain the process for finding the minimum breaker size necessary, please complete the following:
1.
Find your total current load of the circuit (ex: 13.7)
2.
Multiply your current load by 1.25 to find your minimum breaker size (ex: 13.7*1.25=17.125)
3.
Find the correct breaker to match the size you found in #2. If it is not a standard size, per the NEC,
select the next standard size up. For our example we would select a 20A breaker.