EC3-812_65118_EN_R00.doc 

Replacement for R- 

1 / 5  

PCN: 864916      18.03.2009 

 

 

 

EC3-812 Dual Circuit Rack Controller 

Operating Instructions 

GB 

 

Note: This document contains short form instructions for experienced users. 
Use last column in List of Parameters to document your individual settlings. 
More detailed information can be found in the User Manual.  

 

 

 
The 

EC3-812

 dual circuit rack controller is a digital controller for racks in 

commercial refrigeration applications. The controller is designed for split suction 
systems with a common discharge side. Typically the suction side consists of the 
combination of a Low Temperature (LT) rack and a Medium Temperature (MT) 
rack. The LT rack can consist of up to 3 single stage compressors and the MT rack 
of up to 4 single stage compressors. For the two controllers, the control target is to 
maintain the suction pressure at a defined value by varying the available 
compressor capacity. For the measurement of the two suction pressures, two PT4 
pressure sensors with 4 – 20 mA interface can be connected to the controller.  
The rack controller has seven relays outputs to activate the compressors.  Eight 
digital inputs for 24V AC/DC or 230V AC and four digital inputs for 24V AC/DC 
are available, seven for compressor serial alarm, two for low pressure alarm, one 
for high pressure alarm, one for oil level alarm and one for refrigerant level alarm.  
To control the discharge end temperature of compressor from LT rack, three 
temperature inputs are available. Two analogue outputs 0 to 10 V are available to 
control the first compressor of MT and LT rack with an inverter. The optional 
display can show values with a decimal point in the range between -19.9 and +19.9 
otherwise without decimal point. An IR receiver for the optional IR remote control 
unit is build in. The supply voltage is 24 VAC. Transformers for 230V or 110V 
mains supply are available as options. 

 
 

!

  Safety instructions:  

 

Read installation instructions thoroughly. Failure to comply can result in 
device failure, system damage or personal injury. 

 

The product is intended for use by persons having the appropriate 
knowledge and skills.  

 

Ensure electrical ratings per technical data are not exceeded.  

 

Disconnect all voltages from system before installation. 

 

Keep temperatures within nominal limits.  

 

Comply with local electrical regulations when wiring 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

Technical Data 

EC3 Series Controller 

Power supply 

24VAC ±10%; 0.5A; 50/60Hz; Class II 
6.3mm spade earth connector 

Power consumption 

20VA max. 

Communication TCP/IP 

Ethernet 

10MBit/s 

Plug-in connector size  Removable screw terminals 

wire size 0.14 … 1.5 mm

2

 

Temperatures: 

storage 
operating 

 
   -20 … +65°C 
 

0 … +60°C 

Humidity 

0…80%  r.h.  non condensing 

Protection class 

IP20 

Inputs 

Feedback failure contact for compressor B1 to B3 and 
A1 to A4, low-pressure alarm contact A, low-pressure 
alarm contact B, high-pressure alarm contact, oil level 
alarm contact and refrigerant level alarm contact 

Switch 

8 x 24V AC / DC or 230V AC 
4 x 24V AC/DC 

Temperature sensor 
inputs 

NTC ( 1M at 25°C for temperature input 1 to 4: 
discharge temperature; 10K  at 25°C for temperature 
input 5 and 6) 

Pressure transmitter 
inputs 

2 x 24VDC, 4...20mA 

Outputs 

8 x Relays SPDT 
I

max

 = 8A res (2A), VAC max = 250V : 

Compressor relays B1 to B3, A1 to A4 

ECD-000 Display Unit 

Power Supply 

From EC3 via connecting cable 

Display 

2½-digit red LED with decimal point 
reversible between °C and °F 

LED indicators 

Controller 1, Controller 2, p bar, Alarm, IR status 

Temp. &  Humidity 

Identical to EC3 specifications above 

Protection class 

IP65 (front protection with gasket) 

Connecting cable 

ECC-N10 (1m), ECC-N30 (3m), ECC-N50 (5m) or 
CAT5 cable with RJ45 connectors 

Mounting 

The EC3 can be mounted onto a standard DIN rail. 

 

 
 
The ECD-000 can be mounted in panels 
with a 71x29 mm cutout. See dimensional 
drawing below for space requirements 
including rear connectors. 
Push controller into panel cutout. (1) 
Make sure that mounting lugs are flush with 
outside of controller housing 
Insert allen key into front panel holes and 
turn clockwise. Mounting lugs will turn and 
gradually move towards panel (2) 
Turn allen key until mounting lug barely 
touches panel. Then move other mounting 
lug to the same position (3) 
Tighten both sides very carefully until 
display is secured. Do not over tighten as 
mounting lugs will break easily. 

 
 

Summary of Contents for EC3 Series

Page 1: ...jury The product is intended for use by persons having the appropriate knowledge and skills Ensure electrical ratings per technical data are not exceeded Disconnect all voltages from system before installation Keep temperatures within nominal limits Comply with local electrical regulations when wiring Technical Data EC3 Series Controller Power supply 24VAC 10 0 5A 50 60Hz Class II 6 3mm spade eart...

Page 2: ...exit without modifying any parameter Do not press any button for at least 60 seconds TIME OUT Press ESC on IR remote control Special Functions The Clear Alarm function has been replaced by the Special Functions mode The Special Functions can be activated by Press and together for more than 5 seconds A flashing 0 is displayed Press or until the password is displayed default 12 If password was chang...

Page 3: ...ta entry EMS allows data entry in sec Unit on ECD 000 data entry EMS allows data entry in 1000hr Unit on ECD 000 data entry EMS allows data entry in hr F MODULATING PARAM C2 Min Max Unit Def Custom F0 Compressor INV setpoint 1 0 50 0 bar 3 0 valid only for dead band control c3 2 not valid for P c3 0 and PI control c3 1 with P PI control the modulating set point is the P0 parameter F1 Compressor IN...

Page 4: ...ciated with compressor A3 has changed into alarm state safety chain E4 Feedback alarm 4 Controller 2 Digital input associated with compressor A4 has changed into alarm state safety chain n1 Service alarm compressor 1 Controller 1 Compressor B1 operating time higher than run limit Controller 2 Compressor A1 operating time higher than run limit n2 Service alarm compressor 2 Controller 1 Compressor B...

Page 5: ...sername or password A username and password will be requested upon the initial request to any of the other WebPages The factory default settings are Username EmersonID Password 12 The default settings may be modified in the Display configuration page Press the tabs at the top of the Monitoring page with a left click of the mouse button to enter the respective Webpage The parameters will be visuali...

Reviews: