EC2-742 Condenser Controller 

Operating Instructions 

GB 

Note: This document contains short form instructions for experienced users. 
Use last column in List of Parameters to document your individual settings. 
More detailed information can be found in the User Manual.  

 

The 

EC2-742

 controller is for use in condensers with speed controlled fan(s). 

Based on the input signal from a pressure transmitter (1) an analogue 0…10 V 
output signal is provided, which can be used for fan speed power modules (3) as 
the FSP-series from EMERSON, see following drawing: 

 

The PT pressure transmitter (1) senses condensing pressure and feeds the signal 
into a proportional control loop with proportional band (P1) around setpoint (P0). 
This control loop generates a 0…10V output signal to modulate the speed of 
condenser fan motor(s) (3) by using the FSP Fan Speed Power Module (10). 
Digital outputs allow to switch a stage solenoid (5) and a sprinkler valve (4).  
 

Sprinkler 

Solenoid 

2-stage 

Solenoid 

Fan 

Speed 

Output 

 

    Condensing 

Pressure

 
P8 is the setpoint and P9 the differential to activate a sprinkler. P3 is the setpoint 
and P2 the differential to activate the solenoid valve for two stage condenser 
operation. 
A NTC temperature sensor (2) may be attached for ambient air temperature 
measurement. This can be used for setpoint floating. Depending on ambient 
temperature, the condensing pressure setpoint may be lowered in a controlled way 
resulting in a reduction of energy consumption of the overall system. 
A fast recovery procedure can be used to immediately switch off fan(s) when the 
condensing pressure falls below a set limit. Similarly an emergency routine can be 
activated automatically if the condensing pressure exceeds a definable limit. 

!

  Safety instructions:  

 

Read installation instructions thoroughly. Failure to comply can result in 
device failure, system damage or personal injury. 

 

The product is intended for use by persons having the appropriate 
knowledge and skills.  

 

Ensure electrical ratings per technical data are not exceeded.  

 

Disconnect all voltages from system before installation. 

 

Keep temperatures within nominal limits.  

 

Comply with local electrical regulations when wiring 

Technical data: 

Power supply 

24VAC ±10%; 50/60 Hz; Class II 

Power consumption 

4VA max. 

Communication TCP/IP 

Ethernet 

10MBit/s 

Terminals 

Removable screw terminals

 

wire size 0.14 … 1.5 mm

2

 

Temperature  
     storage 
     operating 

 

 -20 … +65°C 

 

0 … +60°C 

Pressure sensor input 

24VDC, 4 … 20mA 

Temperature sensor input  NTC (10K  at 25°C ) 
Condenser and sprinkler 
output relays 

SPDT contacts, AgNi 
Inductive (AC15) 250V / 2A 
Resistive (AC1) 250V / 8A; 12A total return current

Fan variable output signal  0 … 10V;  (3mA max) 
Digital inputs 

Volt free contacts 5V/0,1mA 

Humidity    

0 … 80% rh. non condensing 

Protection class 

IP65 (front protection with gasket) 

Mounting 

The EC2-742 can be mounted in panels with a 71 x 
29 mm cutout. See dimensional drawing below for 
space requirements including rear connectors. 
Push controller into panel cutout.(1) 
Make sure that mounting clamps are flush with 
outside of controller housing 
Insert allen key into front panel holes and turn 
clockwise. Mounting clamp will turn and gradually 
move towards panel (2) 
Turn allen key until mounting clamp barely touches 
panel. Then move other mounting clamp to the same 
position (3). Tighten both sides very carefully until 
controller is secured. Do not over tighten as 
mounting clamps will break easily. 
 

 

Electrical Installation 

 

Refer to the electrical wiring diagram for electrical connections. A copy of this 
diagram is labelled on the controller. 
Use connection wires/cables suitable for 90°C operation (EN 60730-1). 
EC2 analog inputs are for dedicated sensors only and should not be connected to 
any other devices. Volt free digital inputs should only be connected to serial 
control loops or relays with gold contacts. They should not be connected to any 
other devices 

Important:

 Keep controller and sensor wiring well separated from mains wiring. 

Minimum recommended distance 30mm. 

Warning:

 Use a class II category transformer for 24VAC power supply 

(EN 60742). Do not ground the 24VAC lines. We recommend to use one 
transformer per EC2 controller and to use separate transformers for 3

rd

 party 

controllers, to avoid possible interference or grounding problems in the power 
supply. Connecting any EC2 inputs to mains voltage will permanently damage the 
EC2. 
 
 

Summary of Contents for EC2-742

Page 1: ... from system before installation Keep temperatures within nominal limits Comply with local electrical regulations when wiring Technical data Power supply 24VAC 10 50 60 Hz Class II Power consumption 4VA max Communication TCP IP Ethernet 10MBit s Terminals Removable screw terminals wire size 0 14 1 5 mm2 Temperature storage operating 20 65 C 0 60 C Pressure sensor input 24VDC 4 20mA Temperature sen...

Page 2: ...s the current TCP IP address 2 Set the controller s TCP IP address to 192 168 1 101 default value This change is only temporary A power down will reset the previous address 3 Resets all parameters to the factory default setting The controller will indicate oF during the reset and the valve will close Display of Data The data to be permanently shown on the display can be selected by the user parame...

Page 3: ...overy Activates sprinkler valve 9 9 50 bar 50 P9 High pressure recovery dead band Activates sprinkler valve 0 10 0 bar 2 0 A ALARM PARAMETERS A2 Minimum condensing pressure alarm limit 1 0 50 bar 10 0 A3 Maximum condensing pressure alarm limit 1 0 50 bar 27 A4 1 Delay time for minimum pressure alarm limit 0 99 10sec 0 A5 1 Delay time for maximum pressure alarm limit 0 99 10sec 0 A9 2 Fan run limit...

Page 4: ...re it is not necessary to enter a username or password A username and password will be requested upon the initial request to any of the other WebPages The factory default settings are Username EmersonID Password 12 The default settings may be modified in the Display configuration page Press the tabs at the top of the Monitoring page with a left click of the mouse button to enter the respective Web...

Reviews: