E300 Installation and Commissioning Guide
17
Issue Number: 1
2.10 EMC filters
2.10.1 Internal EMC filter
It is recommended that the internal EMC filter be kept in place unless there is a specific reason for removing it, for example the drive is part of a
Regen system or there is excessive ground leakage current in the system.
The internal EMC filter reduces radio-frequency emission into the line power supply. Where the motor cable is short, it permits the requirements of EN
61800-3:2004 to be met for the second environment. For longer motor cables the filter continues to provide a useful reduction in emission levels, and
when used with any length of shielded motor cable up to the limit for the drive, it is unlikely that nearby industrial equipment will be disturbed. It is
recommended that the filter be used in all applications unless the instructions given above require it to be removed, or where the ground
leakage current is unacceptable.
2.10.2 Standard external EMC filter
The external EMC filter for all drive size can be either footprint or bookcase mounted, the details for each EMC filter is provided in the following.
Table 2-9 External EMC filter data
The external EMC filters for sizes 3 to 6 can be footprint mounted or bookcase mounted.
2.10.3 Compact external EMC filters
The external Compact EMC filter for size 3, 4 and 5, drives can be bookcase mounted, the details for each of the Compact EMC filters is provided
following.
Table 2-10 External Compact EMC filter data
N
When using the external Compact EMC filters an additional AC input line reactor is required which is selected to meet the requirements of EN 12015
If the drive is used with ungrounded (IT) supplies, the internal EMC filter must be removed unless additional motor ground fault protection
is installed.
The power supply must be removed prior to removing the internal EMC filter.
WARNING
WARNING
Model
CT part number
Weight
kg
Ib
200 V
03200050 to 03200106
4200-3230
1.9
4.20
04200137 to 04200185
4200-0272
4.0
8.82
05200250
4200-0312
5.5
12.13
06200330 to 06200440
4200-2300
6.5
14.3
07200610 to 07200830
4200-1132
6.9
15.2
400 V
03400025 to 03400100
4200-3480
2.0
4.40
04400150 to 04400172
4200-0252
4.1
9.04
05400270 to 05400300
4200-0402
5.5
12.13
06400350 to 06400470
4200-4800
6.7
14.8
07400660 to 07401000
4200-1132
6.9
15.2
575 V
05500030 to 05500069
4200-0122
7.0
15.4
06500100 to 06500350
4200-3690
7.0
15.4
07500440 to 07500550
4200-0672
690 V
07600190 to 07600540
4200-0672
Model
CT part number
Weight
kg
lb
400 V
03400025 to 03400100
4200-6126
0.4
0.88
4200-6219
0.6
1.32
04400150 to 04400172
4200-6220
0.7
1.54
05400270 to 05400300
4200-6221-01
1.7
3.75
NOTE
Summary of Contents for E300 Series
Page 211: ......
Page 212: ...0479 0005 01 ...