XW60K 110918 V14.7 EMERSON092718 V14.7
XW60K
11/12
Label
Name
Range
Default
Level
Delay of temperature alarm at start up
0.0 to 23h50min, res. 10 min
2.30
Pr2
Probe for temperat. alarm of condenser
nP; P1; P2; P3; P4
P4
Pr2
Condenser for low temperat. alarm
[-55.0 to 150.0°C]
[-67 to 302°F]
-58
Pr2
Condenser for high temperat. alarm
[-55.0 to 150.0°C]
[-67 to 302°F]
230
Pr2
Differential for condenser temperature alarm
recovery
[0.1 to 25.5°C]
[1 to 45°F]
10
Pr2
Condenser temperature alarm delay
0 to 254 min , 255=nU
15
Pr2
Delay of cond. temper. alarm at start up
0.0 to 23h50min, res. 10 min
2.30
Pr2
Solenoid off because of condenser low
temperature alarm
n(0); Y(1)
no
Pr2
Compr. off for condenser high temperature alarm
n(0); Y(1)
no
Pr2
AUXILIARY OUTPUT
Alarm relay disabling
n=no; Y=yes
yes
Pr2
Fourth relay configuration (22-23)
ALr = alarm; dEF = do not select it; Lig =Light; AUS =AUX;
onF=always on; Fan= do not select it; db = the output is set as heat;
Cp2=second compressor
dF2 = second defrost
LiG
Pr2
Alarm relay polarity (if oA3=ALr)
oP; CL
CL
Pr2
DIGITAL INPUT
Digital input polarity
oP=opening;CL=closing
CL
Pr1
Digital input configuration on KeyPad
EAL; bAL; PAL; dor; dEF; ES: Htr; FAN;ONF; AUS; LHT
EAL
Pr1
Digital input alarm delay
0 to 255 min
15
Pr1
Second Digital input on base
n , y
no
Pr2
Digital input polarity
oP=opening;CL=closing
CL
Pr1
Second Digital input configuration
EAL; bAL; PAL; dor; dEF; ES: Htr; FAN;ONF; AUS; LHT
dor
Pr1
Digital input alarm delay
0 to 255 min
0
Pr1
Number of activation of pressure switch
0 to 15
15
Pr2
Compress and fan status when open door
no; FAn; CPr; F_C
F-C
Pr2
Regulation restart with door open alarm
n; Y
yes
Pr2
Light off during energy saving status
n; Y
no
Pr2
Differential for Energy Saving
[-30 to 30°C] [-54 to 54°F]
0
Pr2
*
Current hour
read only (after first set up)
-
rtc
*
Current minute
read only (after first set up)
-
rtc
*
Current day
read only (after first set up)
-
rtc
*
Day of the month
read only (after first set up)
-
rtc
*
Month
read only (after first set up)
-
rtc
*
Year
read only (after first set up)
-
rtc
*
First weekly holiday
Sun to SAt; nu
nu
rtc
*
Second weekly holiday
Sun to SAt; nu
nu
rtc
*
Energy Saving cycle start during workdays
0.0 to 23h50min
0
rtc
*
Energy Saving cycle length during workdays
0.0 to 24h00min
0
rtc
*
Energy Saving cycle start on holidays
0.0 to 23h50min
0
rtc
*
Energy Saving cycle length on holidays
0.0 to 24h00min
0
rtc
*
1
st
workdays defrost start
0.0 to 23h50min; nu
6.0
rtc
*
2
nd
workdays defrost start
0.0 to 23h50min; nu
13.0
rtc
*
3
rd
workdays defrost start
0.0 to 23h50min; nu
21.0
rtc
*
4
th
workdays defrost start
0.0 to 23h50min; nu
0.0
rtc
*
5
th
workdays defrost start
0.0 to 23h50min; nu
0.0
rtc
*
6
th
workdays defrost start
0.0 to 23h50min; nu
0.0
rtc
*
1
st
holiday defrost start
0.0 to 23h50min; nu
6.0
rtc
*
2
nd
holiday defrost start
0.0 to 23h50min; nu
13.0
rtc
*
3
rd
holiday defrost start
0.0 to 23h50min; nu
21.0
rtc
*
4
th
holiday defrost start
0.0 to 23h50min; nu
0.0
rtc
*
5
th
holiday defrost start
0.0 to 23h50min; nu
0.0
rtc