Digital controller with off cycle defrost 

 

XW20LS 

 

1.

 

GENERAL WARNING 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This manual is part of the product and should be kept near the instrument for easy and quick 

reference. 

 

The instrument shall not be used for purposes different from those described hereunder. It cannot be 

used as a safety device. 

 

Check the application limits before proceeding. 

 

Dixell Srl reserves the right to change the composition of its products, even without notice, ensuring 

the same and unchanged functionality.  

1.2

 

 SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden 

temperature changes with high atmospheric humidity to prevent  formation of condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.r.l.” (see 

address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from each 

other, without crossing or intertwining. 

 

In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel 

with inductive loads could be useful. 

2.

 

GENERAL DESCRIPTION 

Model  XW20LS,  format 38x185mm, is a digital thermostat with off cycle defrost designed for 

refrigeration applications at normal temperature. It has 2 relay outputs to control compressor and light.. 

It could be provided with a Real Time Clock which allows programming of up to 6 daily defrost cycles, 

divided into holidays and workdays. A “Day and Night” function with two different set points is fitted for 

energy saving. It is also provided with up to 2 NTC or PTC probe inputs, the first one for temperature 

control, the  second one, to be located onto the evaporator  and  to control the defrost termination 

temperature.  The  digital input can operate as third temperature probe,  to  signal the condenser 

temperature alarm or to display a temperature. 

The HOT KEY output allows to connect the unit, by means of the external module XJ485-CX,  to a 

network line ModBUS-RTU compatible such as the 

dIXEL 

monitoring units  of X-WEB family. It 

allows to program the controller by means the HOT KEY programming  keyboard.  

The instrument is fully configurable through special parameters that can be easily programmed 

through the keyboard. 

3.

 

CONTROLLING LOADS 

3.1

 

COMPRESSOR 

The regulation is performed according to 

the temperature measured by the 

thermostat probe with a positive 

differential from the set point: if the 

temperature increases and reaches set 

point plus differential the compressor is 

started and then turned off when the 

temperature reaches the set point value 

again. 

 

In case of fault in the thermostat probe the start and stop of the compressor are timed through 

parameters “COn” and “COF”. 

3.2

 

DEFROST  

Defrost is performed through a simple stop of the compressor. The defrost interval depends on the 

presence of the RTC (optional). If the RTC is present is controlled by means of parameter “EdF”:  

-

 

with EdF=in the defrost is made every “IdF” time – standard way for controller without RTC. 

-

 

with EdF = “rtc”, the defrost is made in real time depending on the hours set in the parameters 

Ld1..Ld6 on workdays and in Sd1…Sd6 in holidays;  

Other parameters are used to control defrost cycles: its maximum length (MdF) and two defrost 

modes: timed or controlled by the evaporator’s probe (P2P).  

4.

 

FRONT PANEL COMMANDS 

4.1

 

STANDARD FRONTAL PANEL  

 

4.2

 

STEEL FINISHING 

 

 

: To display target set point; in programming mode it  selects a parameter  or confirm an 

operation. 

 (DEF) 

To start a manual defrost 

 

 (UP): To see the max. stored temperature; in programming mode it browses the parameter 

codes or increases the displayed value. 

 (DOWN) To see the min stored temperature; in programming mode it browses the parameter 

codes or decreases the displayed value. 

 

To switch the instrument off.  

 

To switch the light. 

KEY COMBINATIONS: 

  

 

  

To lock & unlock the keyboard. 

 

+

  

 

To enter in programming mode. 

  

+

  

 

To return to the room temperature display. 

4.3

 

USE OF LEDS 

Each LED function is described in the following table. 

LED  MODE 

FUNCTION 

 

ON 

Compressor enabled 

 

Flashing  Anti-short cycle delay enabled 

 

ON 

Defrost enabled 

 

Flashing  Drip time in progress 

  ON 

An alarm is occurring 

  ON 

Continuous cycle is running 

  ON 

Energy saving enabled 

 

ON 

Light on 

°C/°F  ON 

Measurement unit 

°C/°F  Flashing  Programming phase 

5.

 

MAX & MIN TEMPERATURE MEMORIZATION 

5.1

 

HOW TO SEE THE MIN TEMPERATURE 

1. 

 

Press and release the 

n

 key. 

2. 

 

The “Lo” message will be displayed followed by the minimum temperature recorded. 

3. 

 

By pressing the 

n

 key again or by waiting 5s the normal display will be restored. 

5.2

 

HOW TO SEE THE MAX TEMPERATURE 

1. 

 

Press and release the 

o

 key. 

2. 

 

The “Hi” message will be displayed followed by the maximum  temperature recorded. 

3. 

 

By pressing the 

o

 key again or by waiting 5s the normal display will be restored. 

5.3

 

HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED 

1.

 

Hold press the SET key for more than 3s, while the max. or min temperature is displayed. (rSt 

message will be displayed) 

2.

 

To confirm the operation the “rSt” message starts blinking and the normal temperature will be 

displayed. 

6.

 

MAIN FUNCTIONS 

6.1

 

TO SET THE CURRENT TIME AND DAY (ONLY FOR INSTRUMENTS 

WITH RTC) 

When the instrument is switched on, it’s necessary to program the time and day. 

1.

 

Enter the Pr1 programming menu, by pushing the SET + 

keys for 3s. 

2.

 

The rtc parameter is displayed. Push the SET key to enter the real time clock menu. 

3.

 

The Hur (hour) parameter is displayed. 

4.

 

Push the SET and set current hour by the UP and Down keys, then push SET to confirm 

the value.. 

5.

 

Repeat the  same operations on the Min (minutes) and dAy (day) parameters. 

To exit: Push SET+UP keys or wait for 15 sec without pushing any keys. 

6.2

 

HOW TO SEE THE SET POINT 

 

1.

 

Push and immediately release the SET key: the display will show the Set 

point value; 

2.

 

Push and immediately release the SET key or wait for 5 seconds to  

display the probe value again. 

6.3

 

HOW TO CHANGE THE SET POINT 

1.

 

Push the SET key for more than 2 seconds to change the Set point value; 

2.

 

The value of the set point will be displayed and the “°C” or “°F” LED starts blinking; 

3.

 

To change the Set value push the 

or 

n

 arrows within 10s. 

4.

 

To memorise the new set point value push the SET key again or wait 10s. 

6.4

 

HOW TO START A MANUAL DEFROST 

 

Push the DEF key for more than 2 seconds and a manual defrost will start. 

6.5

 

HOW TO CHANGE A PARAMETER VALUE 

To change the parameter’s value operate as follows:  

1592027320 XW20LS RTC GB r1.0 18.03.2015 

XW20LS 

1/5 

Summary of Contents for Dixell XW20LS

Page 1: ...ameter EdF with EdF in the defrost is made every IdF time standard way for controller without RTC with EdF rtc the defrost is made in real time depending on the hours set in the parameters Ld1 Ld6 on workdays and in Sd1 Sd6 in holidays Other parameters are used to control defrost cycles its maximum length MdF and two defrost modes timed or controlled by the evaporator s probe P2P 4 FRONT PANEL COM...

Page 2: ... percentage of visualization rEd X REP display optional P1 P2 P3 P4 SET dtr it selects which probe is displayed by X REP P1 Thermostat probe P2 Evaporator probe P3 Third probe only for model with this option enabled P4 NOT SET IT SET set point dtr percentage of visualization dLy Display delay 0 20 0m resul 10s when the temperature increases the display is updated of 1 C 1 F after this time dtr Per...

Page 3: ...strument will wait until the MdF safety time is expired 8 6 INVERSION OF THE KIND OF ACTION HEATING COOLING i1F Htr This function allows to invert the regulation of the controller from cooling to heating and viceversa 8 7 ENERGY SAVING i1F ES The Energy Saving function allows to change the set point value as the result of the SET HES parameter sum This function is enabled until the digital input i...

Page 4: ...Vac connect to terminals 5 6 The X REP output is optional 17 DEFAULT SETTING VALUES Label Name Range C F Level Set Set point LS US 3 0 rtc Real time clock menu Pr1 Hy Differential 0 1 25 5 C 1 255 F 2 0 Pr1 LS Minimum set point 50 C SET 58 F SET 50 0 Pr2 US Maximum set point SET 110 C SET 230 F 110 Pr2 Ot Thermostat probe calibration 12 12 C 120 120 F 0 0 Pr1 P2P Evaporator probe presence n not pr...

Page 5: ... Sd5 5th holiday defrost start 0 23h 50 min nu 0 0 rtc Sd6 6th holiday defrost start 0 23h 50 min nu 0 0 rtc Adr Serial address 1 247 1 Pr2 PbC Kind of probe Ptc ntc ntc Pr2 onF on off key enabling nu oFF ES oFF Pr2 dP1 Room probe display Pr2 dP2 Evaporator probe display Pr2 dP3 Third probe display Pr2 rSE Real set actual set Pr2 rEL Software release 1 8 Pr2 Ptb Map code Pr2 Only for model with re...