Emerson Dixell XRi77CX Installing And Operating Instructions Download Page 7

 

1592020670 XRi77CX-CH GB r1.1 15.10.2019

 

XRi77CX-CH

 

7/9

 

 

22.

 

DEFAULT SETTING VALUES 

LABEL 

Description 

VALUE 

LEVEL 

SEt 

Regulation Set Point 

-20.0 

 

rtC 

RTC menu visualization 

 

Pr1 

LS 

Minimum Set point 

-30.0 

Pr2 

US 

Maximum Set point 

10.0 

Pr2 

Hy 

Differential for normal regulation 

1.0 

Pr1 

odS 

Outputs delay activation after power on 

Pr2 

AC 

Anti-short cycle delay 

Pr2 

AC1 

Anti-short cycle delay for second compressor 

Pr2 

MCo 

Maximum time with compressor on 

Pr2 

rtr 

Percentage for regulation=F(P1; P2) (100=P1; 0=P2) 

100 

Pr2 

CCt 

Maximum duration for Pull Down 

3.00 

Pr1 

CCS 

Differential for Pull Down (SET+CCS or 

SET+HES+CCS) 

-2.0 

Pr1 

oHt 

Threshold for automatic activation of Pull Down in 

normal mode (SET+HY+oHt) 

10.0 

Pr2 

Con 

Compressor ON time with faulty probe 

30 

Pr2 

CoF 

Compressor OFF time with faulty probe 

Pr2 

PbC 

Probe selection 

ntC 

Pr2 

ot 

Probe P1 calibration 

0.0 

Pr1 

P2P 

Probe P2 presence 

yes 

Pr2 

oE 

Probe P2 calibration 

0.0 

Pr2 

P3P 

Probe P3 presence 

no 

Pr2 

o3 

Probe P3 calibration 

0.0 

Pr2 

P4P 

Probe P4 presence 

no 

Pr2 

o4 

Probe P4 calibration 

0.0 

Pr2 

Hy1 

Differential for proportional regulation in normal mode 

1.0 

Pr2 

Fr0 

Frequency output value with compressor stopped 

Pr2 

PMi 

Minimum compressor speed (in percentage) 

20 

Pr2 

PMA 

Maximum compressor speed (in percentage) 

100 

Pr2 

voS 

Compressor speed variation (increment) when 

temperature is increasing 

Pr2 

vo2 

Compressor speed variation (decrement) when 

temperature is decreasing 

Pr2 

vo3 

Compressor speed variation (decrement) after any 

Pull Down 

Pr2 

PdP 

Compressor speed during any Pull Down 

100 

Pr2 

t1F 

Time with compressor speed at PMI before stopping 

the compressor 

Pr2 

SPi 

Compressor speed (in percentage) in case of any 

error probe 

70 

Pr2 

Aod 

Compressor speed (in percentage) during any defrost 

(valid if tdf=in) 

70 

Pr2 

AoF 

Compressor speed during a pre-defrost phase (valid if 

tdf=in) 

50 

Pr2 

tHv 

Maximum time for compressor speed variation 

60 

Pr2 

tLv 

Minimum time for compressor speed variation 

20 

Pr2 

dtC 

Temperature sampling time 

10 

Pr2 

tH1 

Differential for deadlock control 

1.0 

Pr2 

oFS 

Compressor speed increment during any deadlock 

condition (in Hz) 

Pr2 

CMn 

Continuous mode during normal mode 

yes 

Pr2 

CME 

Continuous mode during energy saving mode 

yes 

Pr2 

MnP 

Minimum compressor speed for activating lubrication 

control (valid only for variable speed compressors) 

30 

Pr2 

tMi 

Compressor running time below the MnP threshold 

01:00 

Pr2 

tMA 

Interval of time with compressor a PMA during 

lubrication control 

Pr2 

CF 

Temperature measurement unit: Celsius; Fahrenheit 

°C 

Pr1 

rES 

Temperature resolution: decimal, integer   

dE 

Pr1 

Lod 

Probe displayed on the display 

P1 

Pr1 

dLy 

Display temperature delay 

00:00 

Pr1 

dtr 

Visualization percentage=F(P1; P2) (ex: dtr=1 means 

VALUE=0.01*P1+0.99*P2) 

99 

Pr1 

EdF 

Defrost mode 

in 

Pr2 

tdF 

Defrost type: electrical heating, hot gas 

in 

Pr2 

dFP 

Probe selection for defrost control 

P2 

Pr2 

dtE 

Defrost termination temperature 

4.0 

Pr2 

idF 

Interval between two consecutives defrost cycles 

24 

Pr2 

MdF 

Maximum length for defrost 

45 

Pr2 

dSd 

Start defrost delay 

Pr2 

StC 

Compressor stop time before starting any defrost 

Pr2 

dFd 

Displaying during defrost 

it 

Pr1 

dAd 

Delay for display temperature update after any defrost 

20 

Pr1 

Fdt 

Draining time 

Pr2 

Hon 

Drain heater activated after draining time Fdt (valid if 

oAx=Het) 

00:00 

Pr2 

dPo 

Defrost after power on 

no 

Pr2 

dAF 

Defrost delay after Pull Down 

Pr2 

FAP 

Probe selection for evaporator fan 

P2 

Pr2 

FSt 

Evaporator fan stop temperature 

-10.0 

Pr2 

HyF 

Differential for evaporator fan regulator 

1.0 

Pr2 

FnC 

Evaporator fan mode operation 

O_n 

Pr2 

Fnd 

Evaporator fan delay after defrost 

Pr2 

FCt 

Differential of temperature for forced activation of 

evaporator fan (o=disabled) 

Pr2 

Ft 

Evaporator fan controlled during defrost 

no 

Pr2 

Fon 

Evaporator fan ON time (with compressor OFF) 

Pr2 

FoF 

Evaporator fan OFF time (with compressor OFF) 

Pr2 

FAC 

Probe selection for condenser fan 

nP 

Pr2 

St2 

Regulation Set Point 2 for condenser fan 

35.0 

Pr2 

Hy2 

Differential for Set Point 2 for condenser fan regulator 

1.0 

Pr2 

FCC 

Condenser fan mode operation 

O_n 

Pr2 

FCo 

Condenser fan on after switching off the compressor 

Pr2 

ACH 

Kind of action for auxiliary regulator 

CL 

Pr2 

SAA 

Set point for auxiliary regulator 

0.0 

Pr2 

SHy 

Differential for auxiliary regulator 

1.0 

Pr2 

ArP 

Probe selection for auxiliary regulator 

nP 

Pr2 

Sdd 

Auxiliary regulator disabled during any defrost 

no 

Pr2 

ALP 

Probe selection for temperature alarms 

P1 

Pr1 

ALC 

Temperature alarms configuration: relative, absolute 

rE 

Pr1 

ALU 

Maximum temperature alarm 

8.0 

Pr1 

ALL 

Minimum temperature alarm 

7.0 

Pr1 

AFH 

Temperature alarm recovery differential 

1.0 

Pr1 

ALd 

Temperature alarm delay 

10 

Pr1 

dAo 

Temperature alarm delay after power-on 

24.00 

Pr1 

AP2 

Probe selection for second temperature alarms 

nP 

Pr2 

AL2 

Second low temperature alarm 

-40.0 

Pr2 

AU2 

Second high temperature alarm 

110.0 

Pr2 

AH2 

Differential for second temperature alarm recovery 

1.0 

Pr2 

Ad2 

Second temperature alarm delay 

Pr2 

dA2 

Delay for second temperature alarm after power-on 

01:00 

Pr2 

bLL 

Compressor off due to second low temperature alarm 

no 

Pr2 

AC2 

Compressor off due to second high temperature alarm 

yes 

Pr2 

SAF 

Differential for anti-freezing control 

5.0 

Pr2 

tbA 

Alarm relay switched off by pushing any key 

yes 

Pr2 

oA1 

Relay output oA1 configuration 

LiG 

Pr2 

oA2 

Relay output oA2 configuration 

dEF 

Pr2 

oA3 

Relay output oA3 configuration 

Fan 

Pr2 

oA4 

Relay output oA4 configuration 

ALr 

Pr2 

oAn 

Analogue output configuration 

FrE 

Pr2 

AOP 

Alarm relay polarity 

CL 

Pr2 

i1P 

Digital input 1 polarity 

CL 

Pr1 

i1F 

Digital input 1 configuration 

dor 

Pr1 

did 

Digital inputs 1 alarm delay 

Pr1 

nPS 

Number of pressure alarm switch before stopping the 

regulation (Lock alarm) 

Pr1 

OdC 

Compressor and fan status after door opening 

F-C 

Pr1 

rrd 

Regulation restart after open door alarm 

yes 

Pr1 

HES 

Differential for energy saving mode 

Pr1 

Summary of Contents for Dixell XRi77CX

Page 1: ...t RTC EdF rtC the defrost is real time controlled depending on the hours set in the parameters Ld1 Ld6 for workdays Other parameters are used to control defrosting cycles the maximum length MdF and defrosting modes timed or controlled by the evaporator s probe P2P At the end of defrost dripping time is started its length is set in the Fdt parameter With Fdt 0 the dripping time is disabled 3 2 1 PR...

Page 2: ... to set the regulation HY1 Differential for proportional regulation 0 1 to 25 5 C 1 to 45 F Fr0 Frequency output value with compressor stopped 0 to 50Hz frequency output signal when compressor stopped PMi Minimum compressor speed in percentage 0 to PMA PMA Maximum compressor speed in percentage PMi to 100 voS Signal output variation increment when temperature is increasing if vdC FrE then 1 to 100...

Page 3: ...g mode by pressing the SET DOWN buttons for 3 sec the C or F LED will start blinking 2 Browse to the required parameter and then press the SET button to display its current value 3 Use UP or DOWN buttons to change its value 4 Press SET button to store the new value and move to the following parameter To exit press SET UP buttons or wait for 15 sec without pressing any key NOTE the set value is sto...

Page 4: ... idF is expired tdF Defrost type EL in EL electrical heater in hot gas dFP Probe selection for defrost control nP P1 P2 P3 P4 nP no probe P1 thermostat probe P2 evaporator probe P3 configurable probe P4 Probe on Hot Key plug dtE Defrost end temperature 55 to 50 C 67 to 122 F enabled only when EdF Pb sets the temperature measured by the evaporator probe which causes the end of defrost idF Interval ...

Page 5: ... condition and its signalling When i1F PAL it is the interval of time to calculate the number of pressure switch activation d2d Digital input 2 alarm delay 0 to 255 min delay between the detection of the external alarm condition and its signalling When i1F PAL it is the interval of time to calculate the number of pressure switch activation nPS Number of pressure alarm events before stopping the re...

Page 6: ... and then turn the Controller ON 3 The parameter list of the HOT KEY will be automatically downloaded into the Controller memory The doL message will blink followed a by a flashing End label 4 After 10 seconds the instrument will restart working with the new parameters 5 Remove the HOT KEY NOTE the message Err is displayed for failed programming In this case turn the unit off and then on if you wa...

Page 7: ...ion for defrost control P2 Pr2 dtE Defrost termination temperature 4 0 Pr2 idF Interval between two consecutives defrost cycles 24 Pr2 MdF Maximum length for defrost 45 Pr2 dSd Start defrost delay 0 Pr2 StC Compressor stop time before starting any defrost 5 Pr2 dFd Displaying during defrost it Pr1 dAd Delay for display temperature update after any defrost 20 Pr1 Fdt Draining time 5 Pr2 Hon Drain h...

Page 8: ...in percentage 100 Pr2 voS_nt Compressor speed variation increment when temperature is increasing 1 Pr2 vo2_nt Compressor speed variation decrement when temperature is decreasing 2 Pr2 vo3_nt Compressor speed variation decrement after any Pull Down 5 Pr2 PdP_nt Compressor speed during any Pull Down 100 Pr2 t1F_nt Time with compressor speed at PMI before stopping the compressor 1 Pr2 SPi_nt Compress...

Page 9: ...arity CL Pr2 i2F_nt Digital input 2 configuration EAL Pr2 did_nt Digital inputs 1 alarm delay 1 Pr1 d2d_nt Digital inputs 2 alarm delay 1 Pr2 nPS_nt Number of pressure alarm switch before stopping the regulation Lock alarm 15 Pr1 OdC_nt Compressor and fan status after door opening F C Pr1 rrd_nt Regulation restart after open door alarm yes Pr1 HES_nt Differential for energy saving mode 0 Pr1 LdE_n...

Reviews: