1592020680 XRi60CH EN r2.0 2021.07.14
XRi60CH
9/9
21.
TECHNICAL DATA
FEATURES
DESCRIPTION
Housing
Self-extinguishing PC/PC+ABS
Dimensions
Frontal 38x80 mm; depth 62mm
Mounting
Panel mounting device in a 71x29mm panel cut-out
Degree of Protection
NEMA (UL 50e)
Indoor use only, type 1 enclosure
IP (IEC/EN 60529)
Front panel: IP65; Rear housing: IP00
Power Supply
According to the model: 12VAC/DC, ±10%; 24VAC/DC, ±10%; 110VAC ±10%, 50/60Hz; 230VAC ±10%, 50/60Hz
Overvoltage Category
II
Rated Power
12VAC/DC: 3VA max; 24VAC/DC: 3VA max; 110VAC or 230VAC: 4VA
Rated Impulse Voltage
2500V
Software Class
A
Terminal blocks / Terminal Connections
Plug-in or screw terminal block, wire section between 1 and 2,5 mm2
Max tightening force: 0.5 N*m for 5,0mm pitch
Data Storing
Real Time Clock:
Data maintenance up to 6 months with lithium battery.
Other parameters:
internal EEPROM.
Type of Action
1.B
Pollution Degree
2, non-condensing humidity
Ambient Operating Temperature and
Humidity
IEC/EN
0T60°C; 20-85 rH% (non-condensing humidity)
UL-CAN/CSA
-20T60°C; 20-85 rH% (non-condensing humidity)
Shipping and storage temperature
-40T85°C; 20-85 rH% (non-condensing humidity)
Resistance to Heat
UL 94 V-0
Measurement range
NTC:
-40T110°C, resolution 0.1°C or 1°C (selectable)
PT1000:
-100T150°C, resolution 0.1°C or 1°C (selectable)
PTC:
-50T150°C, resolution 0.1°C or 1°C (selectable)
Accuracy
±0.7°C ±1 digit and relative to the full scale
Inputs
4 NTC, PTC or PT1000 (configurable); 1 voltage free contacts
I/O port
HOT-KEY: MAX voltage allowed is 5 VDC. DO NOT CONNECT ANY EXTERNAL POWER SUPPLY.
Buzzer
Optional
Serial Outputs
TTL standard available on 5-pin port (HOT-KEY connector); Maximum cable length = 2m
Relay Outputs (standard)
Ref
Nominal
UL
IEC
oA1
SPST 20A,
250VAC
Resistive load 16A, 120/250Vac, 100K cycles
Motor load 1HP (16FLA/96LRA), 120Vac, 30K cycles
Motor load 2HP (12FLA/72LRA), 240Vac, 30K cycles
20A, 250Vac, 30K cycles
oA2
SPST 8A,
250VAC
Resistive load 10A, 120/240Vac, 30K cycles
Motor load 1/4HP, 120Vac, 30K cycles
Motor load 1/2HP, 240Vac, 30K cycles
Resistive load 8A, 30Vdc, 30K cycles
8(3)A, 230Vac, 30K cycles
oA3
SPST 5A,
250VAC
Resistive load 5A, 120/250Vac, 30K cycles
Inductive (general purpose) 5A, 120/250Vac, 30K cycles
Motor load 1.9FLA/11.4LRA, 120/250Vac, 30K cycles
Pilot duty 180VA, 250V, 30K cycles
5A, 230Vac, 30K cycles
Maximum ampacity (common terminal 1)
16A
Analogue Outputs
Freq
Frequency output; Supply max voltage = 12Vdc; Max supply current = 10mA; Duty cycle = 50%; Range = 0 to 166 Hz;
Maximum cable length = 10m
Purpose of control
Operating control
Construction of control
Incorporated control, intended to be used in Class I or Class II equipment
Approvals
R290/R600a: relays tested according to IEC EN60079:0 and IEC EN60079:15
IEC/EN 60730-1; IEC/EN 60730-2-9
UL 60730-1; UL 60730-2-9
CAN/CSA-E60730-1; CAN/CSA-E60730-2-9