XRB06CH – XRB07CH 

1/5 

 

DIGITAL CONTROLLERS WITH  

ENERGY SAVING MANAGEMENT 

XRB06CH AND XRB07CH 

1

 

GENERAL WARNINGS.............................................................................................................. 1

 

2

 

GENERAL DESCRIPTION ......................................................................................................... 1

 

3

 

REGULATION ........................................................................................................................... 1

 

4

 

AUTOMATIC SUPER COOLING FUNCTION ............................................................................. 1

 

5

 

DEFROST ................................................................................................................................. 1

 

6

 

FANS ........................................................................................................................................ 1

 

7

 

AUTOMATIC ENERGY SAVING FUNCTION.............................................................................. 1

 

8

 

FRONT PANEL COMMANDS .................................................................................................... 1

 

9

 

PARAMETERS .......................................................................................................................... 2

 

10

 

DIGITAL INPUTS ....................................................................................................................... 3

 

11

 

INSTALLATION AND MOUNTING.............................................................................................. 3

 

12

 

ELECTRICAL CONNECTIONS .................................................................................................. 3

 

13

 

USE THE HOT KEY ................................................................................................................... 4

 

14

 

ALARM SIGNALLING ................................................................................................................ 4

 

15

 

TECHNICAL DATA .................................................................................................................... 4

 

16

 

CONNECTIONS ........................................................................................................................ 4

 

17

 

DEFAULT SETTING VALUES .................................................................................................... 4

 

 

GENERAL WARNINGS 

1.1 

PLEASE READ BEFORE USING THIS MANUAL 

 

This  manual  is  part  of  the  product  and  should  be  kept  near  the  instrument  for  easy  and  quick 
reference. 

 

The instrument shall not be used for purposes different from those described hereunder. It cannot 
be used as a safety device. 

 

Check the application limits before proceeding. 

1.2 

SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do  not  expose  to  water  or  moisture:  use  the  controller  only  within  the  operating  limits  avoiding 
sudden temperature changes with high atmospheric humidity to prevent formation of condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.r.l.” 
(see address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from 
each other, without crossing or intertwining. 

 

In  case  of  applications  in  industrial  environments,  the  use  of  mains  filters  (our  mod.  FT1)  in 
parallel with inductive loads could be useful. 

 

Dixell  Srl  reserves  the  right  to  change  the  composition  of  its  products,  even  without  notice, 
ensuring the same and unchanged functionality. 

GENERAL DESCRIPTION 

The XRB06CXformat 32 x 74 x 60 mm, is microprocessor based controller, suitable for applications on 
medium or low temperature ventilated refrigerating units. It has three relay outputs to control compressor, 
fan, lights or defrost which can be either electrical or reverse cycle (hot gas). The device is also provided 
with 2 NTC probe inputs, the first one for temperature control and the second one to be located onto the 
evaporator,  to  control  the  defrost  termination  temperature  and  to  control  the  ventilators.  It  is  also 
equipped with a couple of configurable digital inputs.  
The XRB07CX has an additional configurable relay. 
With the HOTKEY it’s possible to program the instrument in a quick and easy way. 

REGULATION 

The  regulation  is  performed  according  to 
the  temperature  measured  by  the 
thermostat 

probe 

with 

positive 

differential  from  the  set  point:  if  the 
temperature  increases  and  reaches  set 
point  plus  differential  the  compressor  is 
started  and  then  turned  off  when  the 
temperature  reaches  the  set  point  value 
again. 

 

 
In  case  of  fault  in  the  thermostat  probe  the  start  and  stop  of  the  compressor  are  timed  through 
parameters CY and Cn

AUTOMATIC SUPER COOLING FUNCTION 

This function is used to cool quickly the goods when the cabinet is filled. 
Different parameters are used for this function depending on the working mode: 
Normal mode will use: 1H1S and 1t 
Energy Saving mode will use: 2H2S1t 
Here below the parameter description: 
-

 

1H, 2H overheating before activating the super cooling function: (0.0 to 12.0°C; 0 to 21°F) value 
added to Set-Point to determine the start temperature of sub-cooling cycle. 

-

 

1S, 2S Subcooling: (0.0 to 12.0°C; 0 to 21°F) value subtracted to Set-Point to determine the end 
temperature of sub-cooling cycle. 

-

 

1t maximum duration for super cooling function: 0 to 99 min 

 
If the temperature is higher than SET+HY+1H or HYE+2H, the super cooling function starts and 
the  compressor  is  not  stopped  till  the  temperature  is  1S  or  2S  degrees  below  the  set  point  SET  or 
SET_ES. To disable this function set 1S, 2S=0

DEFROST 

Two defrost modes are available through the td parameter: 

 

td=EL 

 defrost through electrical heater (compressor OFF) 

 

td=in 

 hot gas  defrost (compressor ON).  

Other parameters are used to control the interval  between defrost cycles (id), its maximum length (Md
and two defrost modes: timed or controlled by the evaporator’s probe. At the end of defrost dripping time 
is started, its length is set in the dt parameter. With dt=0 the dripping time is disabled. 

FANS 

With FC parameter it can be selected the fans functioning: 

 

FC=Cn 

 will switch ON and OFF with the compressor and not run during defrost 

 

FC=on 

 fans will run even if the compressor is off, and not run during defrost 

 
After defrost, there is a timed fan delay allowing for drip time, set by means of the Fd parameter. 
 

 

FC=Cy 

 fans will switch ON and OFF with the compressor and run during defrost 

 

FC=oY 

 fans will run continuously also during defrost. 

 
An additional parameter FS provides the setting of temperature, detected by the evaporator probe, above 
which  the  fans  are  always  OFF.  This  is  used  to  make  sure  circulation  of  air  only  if  his  temperature  is 
lower than set in FS

6.1 

FANS CYCLICAL ACTIVATION WITH COMPRESSOR OFF 

When FC=Cn or CY (fans in parallel to the compressor), by means of the Fn and FF parameters the fans 
can carry out on and off cycles even if the compressor is switched off. When the compressor is stopped 
the fans go on working for the Fn time. With Fn=0 the fans remain always off, when the compressor is 
off. 

6.2 

FANS AND DIGITAL INPUT 

When the digital input is configured as door switch (iF=do) fan and compressor status depends on the 
dC parameter value: 

 

dC=no 

 normal regulation 

 

dC=Fn 

 fans OFF 

 

dC=CP 

 compressor OFF 

 

dC=FC 

 compressor and fans OFF 

 

When rd=Y, the regulation restart with door open alarm. 

AUTOMATIC ENERGY SAVING FUNCTION 

 

 

 
 

FROM 

TO 

CHANGED BY 

Standard 

E.S. 

-

 

Push the ECO button  

-

 

Door continuously closed for the Et time 

E.S. 

Standard 

-

 

Push the ECO button 

-

 

Controller in ES mode for the St time 

-

 

 If the controller is in ES and the door is open more than do time, 
the controller restart standard set point. 

 
NOTE: the cycles (ES 

→ Standard mode → ES ….) are always operating with 

iF or 2F=do and Et and 

St different from zero. 
With  Et  or  St=0  the  controller  doesn’t  change  the  operating  mode,  and  it’s  possible  to  pass  from  the 
standard mode to E.S. by using the ECO button or with iF or 2F=ES
 
Note:  the  energy  saving  status  is  saved  in  EEPROM  to  resume  previous  operation  if  a  power  failure 
occurs. 

FRONT PANEL COMMANDS 

 

 

 

 

To display target set point, in programming mode it selects a parameter or 
confirm an operation. 

Summary of Contents for Dixell XRB06CH

Page 1: ...ckly the goods when the cabinet is filled Different parameters are used for this function depending on the working mode Normal mode will use 1H 1S and 1t Energy Saving mode will use 2H 2S 1t Here below the parameter description 1H 2H overheating before activating the super cooling function 0 0 to 12 0 C 0 to 21 F value added to Set Point to determine the start temperature of sub cooling cycle 1S 2...

Page 2: ... probe presence n Y n not present Y probe configured as present F3 Third probe calibration 9 9 to 9 9 C 17 to 17 F allows to adjust possible offset of the second probe od Outputs activation delay at start up 0 to 99 min this function is enabled at the initial start up of the instrument and inhibits any output activation for the period set in the parameter AC Anti short cycle delay 0 to 99 min mini...

Page 3: ...the external alarm condition and its signalling With iF do it represents the delay to activate the door open alarm 2d Digital input 2 delay 0 to 99min with 2F EA bA or PA is the delay between the detection of the external alarm condition and its signalling With iF do it represents the delay to activate the door open alarm dC Compressor and fan status when open door no Fn cP Fc no normal functionin...

Page 4: ...ntal 32x74 mm depth 60mm Mounting panel mounting in a 71x29mm panel cut out Protection IP20 Frontal protection IP65 Connections Screw terminal block 2 5 mm2 wiring Power supply according to the model 230Vac 10 50 60Hz 110Vac 10 50 60Hz Power absorption 3 5VA max Display 2 digits red LED 14 2 mm high Inputs up to 3 NTC or PTC probes Digital input up to 2 free voltage contacts Relay outputs Compress...

Page 5: ... Li AU nF dB C2 d2 AL AP Alarm relay polarity CL oP CL ENERGY SAVING Et Standard to ES mode time with door closed 0 to 99 hours 4 St ES to Standard mode time with door closed 0 to 99 hours 8 ES Differential for energy saving 30 to 30 C 54 to 54 F 3 do Door open time before restoring Standard mode 0 to 255 sec 3 1H Overheating before activating super cooling function 0 1 to 25 0 C 1 to 45 F 10 1S S...

Reviews: