1592040000 XR70T EN v1.1 2019.07.09
XR70T
15/40
Fo1
Evaporator fan ON time in energy saving mode (with compressor OFF)
(0 to 255 min) used
when energy saving status is active.
FF1
Evaporator fan OFF time in energy saving mode (with compressor OFF):
(0 to 255 min) used
when energy saving status is active.
Fd1
Evaporator fan delay:
(0 to 255 sec) delay before activating evaporator fan
Fd2
Evaporator fan delay after closing door:
(0 to 255 sec) delay before activating evaporator fan
and after closing the door
FAC
Probe selection for condenser fan:
(nP; P1; P2; P3; P4)
nP
=no probe;
Px
=
probe “x”. Note:
P4
=Probe on Hot Key plug.
St2
Set Point 2 regulation (for condenser fan):
(-55 to 50°C; -67 to 122°F) setting of temperature
detected by evaporator probe. Above this value of temperature fans are always OFF.
HY2
Set Point 2 differential (for condenser fan):
(0.1 to 25.5°C; 1 to 45°F) differential for evaporator
ventilator regulator
FCC
Condenser fan operating mode:
(Cn; on; CY; oY)
•
Cn
= runs with the compressor and OFF during defrost
•
on
= continuous mode, OFF during defrost
•
CY
= runs with the compressor and ON during defrost
•
oY
= continuous mode, ON during defrost
Fd3
Condenser fan activation delay:
(0 to 255 sec) delay before activating condenser fan
Fd4
Condenser fan deactivation delay:
(0 to 255 sec) delay before deactivating condenser fan
5.1.6 Auxiliary regulator parameters - AUS
ACH Type of control for auxiliary regulator:
(Ht; CL)
Ht
= heating;
CL
= cooling.
SAA
Set Point for auxiliary regulator:
(-55.0 to 150.0°C; -67 to 302°F) it defines the room temperature
set point to switch auxiliary relay.
SHY
Auxiliary regulator differential:
(0.1 to 25.5°C; 1 to 45°F) differential for auxiliary output set point.
•
ACH=CL
, AUX Cut in is [
SAA+SHY
]; AUX Cut out is
SAA
.
•
ACH=Ht
, AUX Cut in is [
SAA
–SHY]
; AUX Cut out is
SAA
.
ArP
Probe selection for auxiliary regulator:
(nP; P1; P2; P3; P4)
nP
= no probe, the auxiliary relay is
switched only by the digital input;
Px
=
probe “x”. Note:
P4
=Probe on Hot Key plug.
Sdd
Auxiliary regulator disabled during any defrost cycle:
(n; Y)
n
= the auxiliary relay operates
during defrost.
Y
= the auxiliary relay is switched off during defrost.
btA
Base time for parameters Ato and AtF:
(SEC; Min)
SEC
= base time is in second; Min = base
time is in minutes.
Ato
Interval of time with auxiliary output ON:
0 to 255 (base time defined in par.
btA
)
AtF
Interval of time with auxiliary output OFF:
0 to 255 (base time defined in par.
btA
)
5.1.7 Alarm configuration parameters
ALP
Probe selection for temperature alarms:
(nP; P1; P2; P3; P4)
nP
=no probe;
Px
=
probe “x”. Note:
P4
=Probe on Hot Key plug.
ALC Temperature alarms configuration:
(Ab, rE)
Ab
= absolute;
rE
= relative.
ALU
High temperature alarm:
when this temperature is reached, the alarm is enabled after the
Ad
delay time.
•
If
ALC=Ab
→
ALL to 150.0°C or ALL to 302°F.
•
If
ALC=rE
→
0.0 to 50.0°C or 0 to 90°F.
ALL
Low temperature alarm:
when this temperature is reached, the alarm is enabled after the
Ad
delay time.
•
If
ALC=Ab
→
-55.0°C to ALU or -67°F to ALU.
•
If
ALC=rE
→
0.0 to 50.0°C or 0 to 90°F.
AFH Temperature alarm differential:
(0.1 to 25.0°C; 1 to 45°F) alarm differential.
ALd
Temperature alarm delay:
(0 to 255 min) delay time between the detection of an alarm condition
and the relative alarm signalling.
dot
Temperature alarm delay when door open:
(0.0 to 24h00min, res. 10 min) delay time between
the detection of a temperature alarm condition and the relative alarm signalling, after starting up the
instrument.
dAo
Temperature alarm delay at start-up:
(0.0 to 24h00min, res. 10 min) delay time between the
detection of a temperature alarm condition and the relative alarm signalling, after starting up the
instrument.
AP2
Probe selection for second temperature alarm:
(nP; P1; P2; P3; P4)
nP
=no probe;
Px
=probe
“x”. Note:
P4
=Probe on Hot Key plug.