1592040000 XR70T EN v1.1 2019.07.09
XR70T
14/40
rEd
Remote probe displayed (for XH-REP):
(P1; P2; P3; P4; SEt; dtr; USr)
Px
=probe “x”;
SEt
=set
point;
dtr
=do not use it.
dLY
Temperature display delay:
(0.0 to 20min00sec, res. 10 sec) when the temperature increases, the
display is updated of 1°C or 1°F after this time.
dtr
Probe visualization percentage, F(P1; P2):
(0 to 100)
with
dtr=1
the display will show this value
VALUE=0.01*P1+0.99*P2
5.1.4 Defrost configuration parameters - dEF
EdF Defrost mode:
in
=fixed intervals;
rtC
=following real time clock
tdF
Defrost type: EL
=electrical heaters;
in
=hot gas;
ALt
=used only for off-cycle defrost
dFP
Probe selection for defrost control:
(nP; P1; P2; P3; P4)
nP
=no probe;
Px
=
probe “x”. Note:
P4
=Probe on Hot Key plug.
dtE
End defrost temperature:
(-55 to 50°C; -67 to 122°F) sets the temperature measured by the
evaporator probe (
dFP
), which causes the end of defrost cycle.
idF
Interval between two successive defrost cycles:
(0 to 255 hours) determines the time interval
between the beginning of two defrosting cycles.
MdF
Maximum length of defrost cycle:
(0 to 255 min; 0 means no defrost) when
P2P=n
(no
evaporator probe presence) it sets the defrost duration, when
P2P=Y
(defrost end based on
evaporator temperature) it sets the maximum length for the defrost cycle.
dSd Start defrost delay:
(0 to 255 min) delay in defrost activation.
StC
Compressor stop before starting any defrost:
(0 to 900 sec) interval with compressor OFF
before activating hot gas cycle
dFd
Display during defrost:
(rt; it; SP; dF)
rt
= real temperature;
it
= start defrost temperature;
SP
= SET-POINT;
dF
= label “
dF
”.
dAd
Temperature display delay after any defrost cycle:
(0 to 255 min) delay before updating the
temperature on the display after the end of any defrost.
Fdt
Draining time:
(0 to 255 min) regulation delay after finishing a defrost phase
Hon
Drain heater enabled after draining time (par. Fdt):
(0 to 255 min) the relative output will stay on
after draining time.
dPo Defrost cycle enebled at stat-up:
(n; Y) enables defrost at power on.
od1
Automatic defrost (at the beginning of any energy saving mode):
(n; Y)
n
=function disabled;
Y
=function enabled
5.1.5 Evaporator and condenser fan configuration parameters - FAn
FAP
Probe selection for evaporator fan:
(nP; P1; P2; P3; P4)
nP
=no probe;
Px
=
probe “x”. Note:
P4
=Probe on Hot Key plug.
FSt
Evaporator fan stop temperature:
(-55 to 50°C; -67 to 122°F) setting of temperature, detected by
evaporator probe. Above this temperature value fans are always OFF.
NOTE: it works only for
the evaporator fan, NOT for the condenser fan.
HYF
Evaporator fan regulator
differential:
(0.1 to 25.5°C; 1 to 45°F) evaporator fan will stop when the
measured temperature (from FAP) is T<FSt-HYF.
FnC
Evaporator fan operating mode:
(Cn; on; CY; oY)
•
Cn
= runs with the compressor, duty-cycle when compressor is OFF (see
FoF
,
Fon
,
FF1
and
Fo1
parameters) and OFF during defrost
•
on
= continuous mode, OFF during defrost
•
CY
= runs with the compressor, duty-cycle when compressor is OFF (see
FoF
,
Fon
,
FF1
and
Fo1
parameters) and ON during defrost
•
oY
= continuous mode, ON during defrost
Fnd
Evaporator fan delay after defrost cycle:
(0 to 255 min) delay before fan activation after any
defrosts.
FCt
Differential for cyclic activation of evaporator fans:
(0 to 50°C)
FSU
Evaporator fan operating mode:
(Std; Fon; FoF)
Std
= standard mode, evaporator fan uses par
FnC
;
Fon
= evaporator Fan always on;
FoF
= evaporator fan always off.
Ft
Evaporator fan controlled during defrost:
(n; Y)
n
= evaporator fan uses par.
FnC
during any
defrost;
Y
= evaporator fan regulator is active during any defrost.
Fon
Evaporator fan ON time in normal mode (with compressor OFF):
(0 to 255 min) used when
energy saving status is not active.
FoF
Evaporator fan OFF time in normal mode (with compressor OFF):
(0 to 255 min) used when
energy saving status is not active.