background image

 

1592009140  XW563L GB r1.2 03.08.2015 

                           XW563L 

1/6 

W

ING

 

XW563L 

1.

 

GENERAL WARNING 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This manual is part of the product and should be kept near the instrument for easy 
and quick reference. 

 

The  instrument  shall  not  be  used  for  purposes  different  from  those  described 
hereunder. It cannot be used as a safety device. 

 

Check the application limits before proceeding. 

 

Dixell Srl reserves the right to change the composition of its products, even without 
notice, ensuring the same and unchanged functionality. 

1.2

 

 SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do not expose to water or moisture: use the controller only within the operating limits 
avoiding  sudden  temperature  changes  with  high  atmospheric  humidity  to  prevent  
formation of condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be 
opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to 
“Dixell s.r.l.” (see address) with a detailed description of the fault. 

 

Consider  the  maximum  current  which  can  be  applied  to  each  relay  (see  Technical 
Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far 
enough from each other, without crossing or intertwining. 

 

In case of applications in industrial environments, the use of mains filters (our mod. 
FT1) in parallel with inductive loads could be useful. 

2.

 

GENERAL DESCRIPTION 

Each  model  in  the 

XW500

  series  is  fitted  with  a  Real  Time  Clock  which  allows 

programming  of  up  to  eight  daily  defrost  cycles,  divided  into  holidays  and  workdays.  A 
“Day and Night” function with two different set points is fitted for energy saving.  
Model 

XW563L

38x185

  mm  format,  is  microprocessor  based  controller  suitable  for 

applications on medium or low temperature refrigerating units. It is provided with four relay 
outputs  to  control  compressor,  defrost  -  which  can  be  either  electrical  or  hot  gas  -  the 
evaporator fans and the lights. 
It is also provided with two NTC probe inputs, one for temperature control, one to control 
the defrost end temperature of the evaporator. There are two digital inputs (free contact) 
for the door switch and configurable by parameter. 
The  RS485  output  allows  the  user  to  connect  a 

ModBUS-RTU 

compatible  monitoring 

system and the TTL output allows to programme the parameter list with the 

“Hot Key”.

 

3.

 

CONTROLLING LOADS 

3.1

 

THE COMPRESSOR 

The  regulation  is  performed  according  to  the  temperature  measured  by  the  thermostat 
probe  with  a  positive  differential  from  the  set  point:  if  the  temperature  increases  and 
reaches set point plus differential the compressor is started and then turned off when the 
temperature reaches the set point value again. 
In  case  of  fault  in  the  thermostat  probe  the  start  and  stop  of  the  compressor  are  timed 
through parameters “

COn

” and “

COF

”. 

3.2

 

FAST FREEZING 

When  defrost  is  not  in  progress,  it  can  be  activated  the  keypad  by  holding  the 

o

  key 

pressed for about 3 seconds. The compressor operates in continuous mode for the time 
set through the “

CCt

” parameter. The cycle can be terminated before the end of the set 

time using the same activation key, 

o

 for about 3 seconds. 

3.3

 

DEFROST 

Three  defrost  modes  are  available  through  the  “

tdF

”  parameter:  defrost  with  electrical 

heater,  hot  gas  or  thermostatic  defrost.  The  defrost  interval  is  control  by  means  of 
parameter  “

EdF

”:  (EdF=in)  the  defrost  is  made  every  “

IdF

”  time,  (EdF=Sd)  the  interval 

“IdF” is calculate through Smart Defrost algorithm (only when the compressor is ON and 
the evaporator temperature is bigger than “SdF” parameter). 
At the end of defrost the drip time is controlled through the “

Fdt

” parameter. 

 

3.4

 

CONTROL OF EVAPORATOR FANS 

The fan control mode is selected by means of the “

FnC

” parameter: 

FnC=C-n

  

fans  will  switch  ON  and  OFF  with  the  compressor  and

  not  run

  during 

defrost

:

FnC=C-y

  

fans will run continuously, but not during defrost  

After defrost, there is a timed fan delay allowing for drip time, set by means of the “Fnd” 
parameter. 

FnC=O-n

  

fans will switch ON and OFF with the compressor and 

run

 during defrost; 

FnC=O-y

  

fans will run continuously also during defrost 

An  additional  parameter  “FSt”  provides  the  setting  of  temperature,  detected  by  the 
evaporator probe, above which the fans are always OFF. This can be used to make sure 
circulation of air only if his temperature is lower

 than set in “FSt”. 

 
 

4.

 

KEYBOARD 

 

To  display  and  modify  target  set  point;  in  programming  mode  it  selects  a 
parameter or confirm an operation.  
By holding it pressed for 3s when max or min temperature is displayed it will be 
erased. 
By pressing it when the current time is displayed, it allows the User to re-set the 
current time and three holidays. 
 

 

To  see  the  max.  stored  temperature;  in  programming  mode  it  browses  the 
parameter codes or increases the displayed value. By holding it pressed for 3s 
the fast freezing  cycle is started. 

 

To  see  the  min  stored  temperature;  in  programming  mode  it  browses  the 
parameter codes or decreases the displayed value. 
By holding it pressed for 3s the current time is displayed and it permits the User 
to enter Energy saving, Defrost and Clock parameter menu. 
 

 

By holding it pressed for 3s the defrost is started. 
By  pressing  it  when  the  current  time  is  displayed,  it  allows  the  User    to  set 
defrost times. 
 

 

 
Switch ON and OFF the cold room light. 

 

 
Switch ON and OFF the instrument. 

 

KEY COMBINATIONS 

 

 

 

 

To lock and unlock the keyboard.

 

 

 

 

To enter the programming mode. 

 

 

 

 

To exit the programming mode.

 

 

4.1

 

USE OF LEDS 

Each LED function is described in the following table. 

LED  MODE 

Function 

 

ON 

The compressor is running 

 

FLASHING 

- Programming Phase (flashing with LED 

- Anti-short cycle delay enabled 

  ON 

The fan is running 

  FLASHING 

Programming Phase (flashing with LED 

 

ON 

The defrost is enabled 

 

FLASHING 

Drip time in progress 

 

ON 

The Fast Freezing cycle is enabled 

   ON 

- ALARM signal 
- In “Pr2” indicates that the parameter is also present in “Pr1” 

 
Function of the LEDs placed on the left top side of buttons: 

BUTTON 

MODE 

FUNCTION 

DOWN/CLOCK 

ON

 

Time is displayed 

DOWN/CLOCK 

FLASHING 

Programming time is enabled 

DOWN/CLOCK  SLOW FLASHING  Holiday function is ON 

SET 

FLASHING 

The Set point is displayed and it can be modified  

Summary of Contents for Dixell WING XW563L

Page 1: ...ing the o key pressed for about 3 seconds The compressor operates in continuous mode for the time set through the CCt parameter The cycle can be terminated before the end of the set time using the same activation key o for about 3 seconds 3 3 DEFROST Three defrost modes are available through the tdF parameter defrost with electrical heater hot gas or thermostatic defrost The defrost interval is co...

Page 2: ...ch ON and OFF the light the auxiliary output and the instrument TO UNLOCK THE KEYBOARD Keep the o and n keys pressed together for more than 3s 4 11 ON OFF FUNCTION By pushing the ON OFF key the instrument shows OFF for 5 sec and the ON OFF LED is switched ON During the OFF status all the relays are switched OFF and the regulations are stopped if a monitoring system is connected it does not record ...

Page 3: ...ignalling EdA Alarm delay at the end of defrost 0 255 min Time interval between the detection of the temperature alarm condition at the end of defrost and the alarm signalling dot Delay of temperature alarm after closing the door 0 255 min Time delay to signal the temperature alarm condition after closing the door doA Open door alarm delay 0 254min nu delay between the detection of the open door c...

Page 4: ... the regulation are stopped When the digital input is ON the compressor is always OFF 7 5 CONFIGURABLE INPUT START DEFROST DFR It executes a defrost if there are the right conditions After the defrost is finished the normal regulation will restart only if the digital input is disabled otherwise the instrument will wait until the Mdf safety time is expired 7 6 CONFIGURABLE INPUT ENERGY SAVING ES Th...

Page 5: ...ure switch alarm Alarm output ON Other outputs OFF The alarm message is displayed until the alarm condition is recovery All the alarm messages are showed alternating with the room temperature except for the P1 which is flashing To reset the EE alarm and restart the normal functioning press any key the rSt message is displayed for about 3s 13 1 SILENCING BUZZER Once the alarm signal is detected the...

Page 6: ...110 C 58 230 F 0 32 Pr2 APb Analogue output band width 50 0 110 C 58 230 F 0 Pr2 CAO Input type for the analogue output P1 1r2 P1 Pr2 LAo Minimum current for analog output 4 20 4 Pr2 ANALOGUE INPUTS Ot Thermostat probe calibration 12 0 12 0 C 21 21 F 0 Pr1 OE Evaporator probe calibration 12 0 12 0 C 21 21 F 0 Pr2 P2P Evaporator probe presence n y y Pr2 HES Temperature increase during the Energy Sa...

Reviews: