![Emerson Copeland YF05K1E Application Manuallines Download Page 8](http://html.mh-extra.com/html/emerson/copeland-yf05k1e/copeland-yf05k1e_application-manuallines_101115008.webp)
AGL_Ref_ST_YFK1E_EN_Rev01
3
2
Product description
2.1 Compressor range
These application guidelines cover Copeland scroll compressor models YF*K1E for low-temperature
ref rigeration applications. YF*K1E scroll compressors can be operated with either A1 or A2L
ref rigerants.
Compressor
Cooling capacity* (kW)
Displacement
(m
3
/h)
Motor
R404A
R407A
R407F
R448A
R449A
YF05K1E
1.12
0.98
1.06
0.95
0.95
5.9
TFDN
YF06K1E
1.36
1.22
1.32
1.15
1.14
7.3
TFDN
YF07K1E
1.50
1.34
1.44
1.37
1.36
8.0
TFDN
YF09K1E
1.90
1.68
1.81
1.70
1.70
9.9
TFDN
YF10K1E
2.15
1.92
2.08
1.98
1.97
11.8
TFDN
YF13K1E
2.63
2.35
2.54
2.43
2.43
14.4
TFDN
YF15K1E
3.06
2.88
3.12
3.12
3.10
17.1
TFDN
Table 1: YF*K1E model overview for LT applications with A1 refrigerants
Compressor
Cooling capacity* (kW)
Displacement
(m
3
/h)
Motor
R454C
R455A
R454A
YF05K1E
0.93
1.04
1.20
5.9
TFDN
YF06K1E
1.15
1.28
1.48
7.3
TFDN
YF07K1E
1.27
1.40
1.64
8.0
TFDN
YF09K1E
1.56
1.74
2.02
9.9
TFDN
YF10K1E
1.86
2.05
2.40
11.8
TFDN
YF13K1E
2.27
2.49
2.93
14.4
TFDN
YF15K1E
2.68
2.95
3.48
17.1
TFDN
Table 2: YF*K1E model overview for LT applications with A2L refrigerants
* Refrigerant dew point temperature, evaporating temperature: -35 °C; condensing temperature: 45 °C;
suction gas superheat: 10 K; liquid sub-cooling: 0 K; frequency: 50 Hz.
2.2 Nomenclature
The model designation contains the following technical information about the compressor:
Figure 1: Nomenclature