background image

 

 

© 2017 Emerson Climate Technologies, Inc.

 

AE4-1372 R4 

tube (available from Emerson) and install it in a system 
with the longest connecting lines that are approved for 
the  system.  The  minimum  on  time  becomes  the  time 
required for oil lost during compressor start-up to return 
to the compressor sump and restore a minimal oil level 
that  will  ensure  oil  pick-up  through  the  crankshaft. 
Cycling the compressor for a shorter period than this, for 
instance to maintain very tight temperature control, will 
result  in  progressive  loss  of  oil  and  damage  to  the 
compressor. 

 

ASSEMBLY LINE PROCEDURES 

Installing the Compressor 

Copeland  Scroll  compressors  leave  the  factory 
dehydrated  and  with  a  positive  dry  air  charge.  Plugs 
should  not  be  removed  from  the  compressor  until  the 
compressor has had sufficient time to warm up if stored 
outside  and  is  ready  for  assembly  in  the  unit.  The 
suggested  warm  up  time  is  one  hour  per  4°F  (2K) 
difference between  outdoor  and  indoor  temperature. It 
is  suggested  that  the  larger  suction  plug  be  removed 
first  to  relieve  the  internal  pressure.  Removing  the 
smaller discharge plug could result in a spray of oil out 
of this fitting since some oil accumulates in the head of 
the compressor after Emerson’s run test. The inside of 
both  fittings  should  be  wiped  with  a  lint  free  cloth  to 
remove  residual  oil  prior  to  brazing.  A  compressor 
containing POE oil should never be left open longer than 
5 minutes. 

 

Assembly Line Brazing Procedure 

Following  are

 

the  proper  procedures  for  brazing  the 

suction and discharge lines to a scroll compressor. It is 
important  to  flow  nitrogen  through  the  system  while 
brazing  all  joints  during  the  system  assembly  process. 
Nitrogen displaces the air and prevents the formation of 
copper  oxides  in  the  system.  If  allowed  to  form,  the 
copper  oxide  flakes  can  later  be  swept  through  the 
system  and  block  screens  such  as  those  protecting 
capillary  tubes,  thermal  expansion  valves,  and 
accumulator  oil  return  holes.  Any  blockage  of  oil  or 
refrigerant  may  damage  the  compressor  resulting  in 
failure. 

 

New Installations 

 

The  copper-coated  steel  suction  tube  on  scroll 
compressors can be brazed in approximately the 
same manner as any copper tube. 

 

Recommended brazing materials: Any SIL-FOS® 
material  is  recommended,  preferably  with  a 
minimum  of  5%  silver.  However,  0%  silver  is 
acceptable. 

 

Be sure suction tube fitting I.D. and suction tube 
O.D.  are  clean  prior  to  assembly.  If  oil  film  is 
present  wipe  with  denatured  alcohol,  Dichloro-
Trifluoroethane or other suitable solvent. 

 

Using a double-tipped torch apply heat in Area 1. 
As  tube  approaches  brazing  temperature,  move 
torch flame to Area 2. 

 

Scroll Suction Tube Brazing 

 

Heat  Area  2  until  braze  temperature  is  attained, 
moving  torch  up  and  down  and  rotating  around 
tube as necessary to heat tube evenly. Add braze 
material  to  the  joint  while  moving  torch  around 
joint to flow braze material around circumference. 

 

After  braze  material  flows  around  joint,  move 
torch  to  heat  Area  3.  This  will  draw  the  braze 
material  down  into  the  joint.  The  time  spent 
heating Area 3 should be minimal. 

 

As  with  any  brazed  joint,  overheating  may  be 
detrimental to the final result. 

‘Hipot’ (AC High Potential) Testing 

Copeland  Scroll  compressors  are  configured  with  the 
motor down and the pumping components at the top of 
the  shell.  As  a  result,  the  motor  can  be  immersed  in 
refrigerant  to  a  greater  extent  than  hermetic 
reciprocating  compressors  when  liquid  refrigerant  is 
present in the shell. In this respect, the scroll is more like 
semi-hermetic compressors that have horizontal motors 
partially submerged in oil and refrigerant. 
 
When  Copeland  Scroll  compressors  are  hipot  tested 
with liquid refrigerant in the shell, they can show higher 
levels  of  leakage  current  than  compressors  with  the 
motor  on  top.  This  phenomenon  can  occur  with  any 
compressor when the motor is immersed in refrigerant. 
The level of current leakage does not present any safety 
issue. To lower the current leakage reading, the system 
should  be  operated  for  a  brief  period  of  time  to 
redistribute  the  refrigerant  to  a  more  normal 
configuration  and  the  system  hipot  tested  again.  See 

AE4-1294

  for  megaohm  testing  recommendations. 

Summary of Contents for Copeland Scroll ZO104KCE

Page 1: ...pecially designed rubber grommets Kit 527 0157 00 12 Figure 3 Oil Management Control OMC CO2 12 Figure 4 Suction Side Pressure Relief Valve Requirements 13 Figure 5 Three Phase Power Circuit 14 Figure 6 ZO Compressor Operating Envelope 14 Figure 7 Compressor Electrical Connection 14 Revision Tracking R4 Pg 2 New Pressure Safety Icon added Pg 4 Caution tag added to superheat requirement Pg 4 Notes ...

Page 2: ...e safety instructions Safety Icon Explanation DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION used with the safety alert symbol indicates a hazardous situation which if not avoided could result in minor or moderate injury NOTICE is used to ...

Page 3: ...and refrigeration oils Personal safety equipment must be used Failure to follow these warnings could result in serious personal injury BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system components Personal safety equipment must be used Failure to follow these warning...

Page 4: ... with R 410A air conditioning compressors which operate at similar pressure levels as CO2 compressors CO2 FOR LOW TEMPERATURE APPLICATIONS SUB CRITICAL DX SYSTEM Figure 1 at the end of this bulletin shows a cascade system diagram with HFC refrigerant for the high side and sub critical CO2 for the low stage refrigerant Nomenclature The model designation contains the following technical information ...

Page 5: ... port on the suction Rotalock valve This port is open to the compressor sump no matter what position the valve stem is located The relief valve itself can be remotely located as long as the path from compressor suction sump and the valve is always open 2 This flow path cannot be shut off in any way by a valve Figure 4 represents the correct a and incorrect b way to apply the pressure relief valve ...

Page 6: ...r to Figure 5 for details The terminal box is IP21 for all models from ZO21K to ZO104K The ZO Scroll compressors have three phase induction motors connected in star Copeland Scroll compressors like several other types of compressors will only compress in one rotational direction Three phase compressors will rotate in either direction depending upon phasing of the power Since there is a 50 chance o...

Page 7: ...eatedly reach temperatures above 350 F 176 7 C if the compressor cycles on its internal protection devices This only happens under rare circumstances and can be caused by the failure of system components such as the condenser or evaporator fan or loss of charge and depends upon the type of expansion control Care must be taken to ensure that wiring or other materials that could be damaged by these ...

Page 8: ...l or refrigerant may damage the compressor resulting in failure New Installations The copper coated steel suction tube on scroll compressors can be brazed in approximately the same manner as any copper tube Recommended brazing materials Any SIL FOS material is recommended preferably with a minimum of 5 silver However 0 silver is acceptable Be sure suction tube fitting I D and suction tube O D are ...

Page 9: ...r may be indicated A current imbalance exceeding 20 of the average on the three phases of a three phase compressor should be investigated further A more comprehensive trouble shooting sequence for compressors and systems can be found in Section H of the Electrical Handbook Form No 6400 8 Before replacing or returning a compressor be certain that the compressor is actually defective As a minimum re...

Page 10: ...40V 70W 32 Lead Length 995 0018 00 018 0095 04 240V 70W 48 Lead Length 918 0043 00 018 0095 05 480V 70W 48 Lead Length 918 0043 01 018 0095 06 575V 70W 48 Lead Length 918 0043 02 018 0095 07 120V 70W 48 Lead Length 918 0043 07 018 0095 08 400V 70W 48 Lead Length 018 0095 09 277V 70W 21 Lead Length Table 1 ZO Family Models Model Nominal Horse power Displacement CFH Capacity BTU HR EER Weight LB kg ...

Page 11: ...ime Delay for Low Level Signal 10 seconds Time Delay After Setpoint Recovery 5 seconds Alarm Delay Time Including Alarm Contact 120 seconds Alar Switch SPDT Alarm Contact Rating 10A 120VAC 50 60Hz 5A 250VAC 50 60 Hz 3A 30 VDC Refrigerant Temperature 40 to 180 F 40 C to 82 2 C Maximum Ambient Temperature Storage 40 to 120 F 40 C to 48 9 C Maximum Ambient Temperature Intermittent Duty 40 to 120 F 40...

Page 12: ... 2017 Emerson Climate Technologies Inc 12 AE4 1372 R4 Figure 3 Oil Management Control OMC CO2 Figure 2 Specially designed rubber grommets Kit 527 0157 00 ...

Page 13: ... 2017 Emerson Climate Technologies Inc 13 AE4 1372 R4 Figure 4 Suction Side Pressure Relief Valve Requirements ...

Page 14: ... or services described herein or their use or applicability Emerson Climate Technologies Inc and or its affiliates collectively Emerson as applicable reserve the right to modify the design or specifications of such products at any time without notice Emerson does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of...

Reviews: