Network Wiring and Configuration
XJ Scroll Condensers connect to the E2 with the One-Way Communication Board using
RS485 MODBUS.
Connect the XJ Scroll to the MODBUS network as shown in
Figure 2
. Connect the network
cable to the three-terminal connector on the E2 COM port that has been configured as MOD-
BUS port (COM 2, 4, or 6).
Figure 1 - XJ Scroll Connected to a One-Way Communication Board