1/200 to 1/250. Upper and lower oil traps, double risers and reduced pipe diameters may be required
f or suction lines where long vertical risers cannot be avoided.
All pipes should be adequately supported to prevent sagging which can create oil traps. The
recommended pipe clamp support distance is shown in
Table 21
below:
Tube size
Max distance between
2 clamp supports
1/2" (12.7 mm)
1.20 m
5/8" (16.0 mm)
1.50 m
7/8" (22.0 mm)
1.85 m
1 1/8" (28.5 mm)
2.20 m
Table 21: Maximum distance between 2 clamp supports
NOTE: It is strongly recommended to insulate both the suction and liquid interconnecting
piping between the OLTE unit and the evaporator.
3.2.2 Connection sizes
Figure 29: Connection ports on suction & liquid lines
Unit
Suction inlet
Liquid outlet
OMTE-76D
& OMTE-90D
1 3/8" (34.925 mm)
5/8" (15.875 mm)
OLE-49
1 3/8" (34.925 mm)
1/2" (12.7 mm)
OMTE-152D
& OLTE-82D
1 5/8" (41.275 mm)
7/8" (22.23 mm)
Table 22: Suction & liquid line diameters