C6.1.10/0118-0318/E
3
Installation
WARNING
High pressure!
Injury to skin and eyes possible!
Be careful when opening
connections on a pressurized item.
Copeland EazyCool ZXDI indoor condensing units are delivered with a holding charge of neutral
gas.
The condensing unit should to be installed in a closed machine room. Soundproofing the machine
room is highly recommended because of a potentially high sound production. The room
characteristics must also be taken into account.
It is important to prevent any dirt, dust, plastic bags, leaves or papers from entering the air ducts
and covering or blocking the condenser and its fins. Proper protective end-grids should be used
for this purpose.
A clogged condenser will increase the condensing temperature, thus reducing the cooling
capacity, which could lead to a high-pressure switch tripping. Clean the condenser fins on a regular
basis.
The unit must be installed in such a way that the airflow through the connected air ducts is not
restricted. The incoming air flow must be sufficient to cover the entire air needs of the unit.
3.1 Condensing unit handling
3.1.1 Transport and storage
WARNING
Risk of collapse! Personal injuries!
Move condensing unit only with
appropriate mechanical or handling equipment according to weight. Keep in
the upright position. Stack pallets on top of each other when not exceeding
300 kg. Do not stack single boxes on top of each other. Keep the packaging
dry at all times.
Figure 17: Transport and storage
3.1.2 Weights
Condensing
unit
Net weight*
(kg)
Gross weight**
(kg)
ZXDI040E
138
154
ZXDI050E
142
158
ZXDI060E
146
162
ZXDI075E
152
168
* Product without packaging
** Product including packaging
Table 19: Weights