C6.1.6/0117-1017/E
63
Appendix 6: Alarm menu
Code
Description
Cause
Action
Reset
E01
AI1 error (Probe 1/Suction pressure
transducer failure alarm)
Probe failure or out of
range
Only in digital unit - compressor is
activated according to C23, and
compressor on & off time is according
to D02 & D03
Automatically as soon as the probe restarts
working.
E02
AI2 error (Probe 2/mid-coil
temperature sensor failure alarm)
Probe failure or out of
range
The fan speed control is disabled
Automatically as soon as the probe restarts
working.
E03
AI3 error (Probe 3/discharge line
temperature sensor failure alarm)
Probe failure or out of
range
The discharge temperature control is
disabled
Automatically as soon as the probe restarts
working.
E04
AI4 error (Probe 4/PHE vapour inlet
temperature sensor failure alarm)
Probe failure or out of
range
PHE superheat control is disabled
(ZXLE/ZXME units)
Automatically as soon as the probe restarts
working.
E05
AI5 error (Probe 5/PHE vapour
outlet temperature sensor failure
alarm)
Probe failure or out of
range
PHE superheat control is disabled
(ZXLE/ZXME units)
Automatically as soon as the probe restarts
working.
E06
AI6 error (Probe 6/ambient
temperature sensor failure alarm)
Probe failure or out of
range
The functions related to probe 6
(ambient sensor) are disabled
Automatically as soon as the probe restarts
working.
E07
AI7 error
Probe failure or out of
range
E08
Battery error
E09
Current sensor 1 error
Probe out of range
The functions related to the current
sensor are disabled
Automatically as soon as the probe restarts
working.
E10
Current sensor 2 error
Probe out of range
The functions related to the current
sensor are disabled
Automatically as soon as the probe restarts
working.
E11
Voltage sensor 1 error
Probe out of range
The functions related to the current
sensor are disabled
Automatically as soon as the probe restarts
working.
E12
Voltage sensor 2 error
Probe out of range
The functions related to the current
sensor are disabled
Automatically: as soon as the probe restarts
working.
E13
Voltage sensor 3 error
Probe out of range
The functions related to the current
sensor are disabled
Automatically as soon as the probe restarts
working.
E14-E19
Reserved