33
Installation and Maintenance Instructions
MAN-02-04-99-0712-EN Rev. 1
February 2020
Actuator Configuration
Section 6: Actuator Configuration
6.2.2
Close Limit Configuration by Position
Enter setup configuration:
•
Move switch SW4 to position 2
•
Move switch SW6 to position 1
•
Move switch SW3 to position ON
•
Confirm by pushing ENTER pushbutton SW5
•
When pushing SW5, the red LED switches on for confirmation
•
Exit setup configuration by moving switch SW3 to position 1 or proceed to the
next parameter
6.2.3
Close Limit Configuration
•
Move switch SW3 to position ON
•
Drive the actuator to the closed position using the handwheel
•
Move switch SW4 to position 0
•
Move switch SW6 to position 0
•
Confirm by pushing ENTER pushbutton SW5
•
When pushing SW5, the red LED switches on for confirmation
•
Exit setup configuration by moving switch SW3 to position 1 or proceed with the
next parameter
6.2.4
Open Limit Configuration by Position
•
Move switch SW4 to position 3
•
Move switch SW6 to position 1
•
Move switch SW3 in ON
•
Confirm by pushing ENTER pushbutton SW5
•
When pushing SW5, the red LED switches on for confirmation
•
Exit setup configuration by moving switch SW3 to position 1 or proceed with the
next parameter