Site Preparation
AXP640 Installation and Use (6806800M24E
)
58
To guarantee proper blade operation, you have to make sure that the temperatures at the
locations specified in the following are not exceeded. If not stated otherwise, the temperatures
should be measured by placing a sensor exactly at the given locations.
Table 3-2 Critical Temperature Limits
Component
Temperature Limit
Air inlet (system’s front)
55°C (131 °F)
Air outlet (system's rear)
70°C (158 °F)
>70°C (158 °F) and maximum 90°C (194 °F): the
cables must be isolated and must be approved to be
used in this temperature range.
>70°C (158 °F) and maximum 90° (194 °F): the service
personnel may touch the components: the cables
must be isolated and the "hot surface" icon must be
attached. The cables must be approved to be used in
this temperature range.
Summary of Contents for AXP640-AC2-110VAC
Page 8: ...AXP640 Installation and Use 6806800M24E Contents 8 Contents Contents ...
Page 10: ...AXP640 Installation and Use 6806800M24E 10 List of Tables ...
Page 26: ...Platform Architecture AXP640 Installation and Use 6806800M24E 26 ...
Page 46: ...AXP640 Shelf Description AXP640 Installation and Use 6806800M24E 46 Figure 2 14 AC Inlet 220V ...
Page 52: ...AXP640 Shelf Description AXP640 Installation and Use 6806800M24E 52 ...
Page 76: ...Site Preparation AXP640 Installation and Use 6806800M24E 76 ...
Page 86: ...AXP640 Operations AXP640 Installation and Use 6806800M24E 86 ...
Page 110: ...AXP640 Shelf Installation AXP640 Installation and Use 6806800M24E 110 ...
Page 138: ...FRU Installation AXP640 Installation and Use 6806800M24E 138 ...
Page 189: ......