AXP640 Shelf Description
AXP640 Installation and Use (6806800M24E
)
40
The FTM is hot swappable and may be managed through the IPM Sentry software for hot swap.
If your system is not running high-availability software, behavior of the LED may be
indeterminate. The face plate of the FTM has the following indicators:
2.9
Power Entry Modules (PEMs)
The PEM is a Field Replaceable Unit (FRU) and can be replaced while the system is on, but the
power for the PEM being replaced (PEM A or PEM B) must be shut down at the external source
prior to replacement. Replacement can take place in under 30 minutes by a trained service
person.
For important information on removing power before replacing a PEM, refer to
The PEMs are accessible from the front of the shelf. Power supplied to the PEM enters the
chassis from the rear on the DC inlet 2-hole lugs. A removable plastic housing covers the power
feeds and returns to prevent accidental shorting on the DC inlet. Once power is removed at the
external source, the PEM may be removed and replaced from the front of the shelf.
Table 2-5 FTM LED Status Indicator
FTM LED
LED Color
State/Condition
In-Service (IS)
Green
Off: no service
Glow Steady: service available
Out-of-Service (OOS) and Failure
Red (default)
Off: service available
Glow Steady: no service
Figure 2-9
Fan Tray Module, Rear View
Summary of Contents for AXP640-AC2-110VAC
Page 8: ...AXP640 Installation and Use 6806800M24E Contents 8 Contents Contents ...
Page 10: ...AXP640 Installation and Use 6806800M24E 10 List of Tables ...
Page 26: ...Platform Architecture AXP640 Installation and Use 6806800M24E 26 ...
Page 46: ...AXP640 Shelf Description AXP640 Installation and Use 6806800M24E 46 Figure 2 14 AC Inlet 220V ...
Page 52: ...AXP640 Shelf Description AXP640 Installation and Use 6806800M24E 52 ...
Page 76: ...Site Preparation AXP640 Installation and Use 6806800M24E 76 ...
Page 86: ...AXP640 Operations AXP640 Installation and Use 6806800M24E 86 ...
Page 110: ...AXP640 Shelf Installation AXP640 Installation and Use 6806800M24E 110 ...
Page 138: ...FRU Installation AXP640 Installation and Use 6806800M24E 138 ...
Page 189: ......