2.3.1
Connect to a wired HART interface
You need to initially connect the device to a wired HART interface to define the credentials
that allow it to communicate on a wireless network. You can also define other device
configurations such as sensor type and alert thresholds at this time.
Notes
Use the wired HART interface only for configuration. Dynamic variables (such as measured
vibration parameters) are not updated when communicating on the wired interface.
Procedure
1. Locate the terminals for the communication port on the opposite side of the device.
2. Connect a configuration device to the terminals such as a computer running AMS
Device Manager with a HART
™
modem or an AMS Trex Communicator.
3. Configure the device.
•
To configure the device using AMS Device Manager, see
.
•
To configure the device using AMS Trex Communicator, see
.
Press
Send
to send configuration changes to the monitor.
2.3.2
Set the wireless network configuration
This enables the monitor to communicate with the Emerson Wireless Gateway and with
other systems. This is the wireless equivalent of connecting wires from a transmitter to a
control system input.
Procedure
1. From the Emerson Wireless Gateway, click
System Settings
→
Network
→
Network Settings
to obtain the Network ID and Join Key.
User Guide
Configuration
MHM-97927-PBF
August 2020
MHM-97927-PBF, Rev 1
19
Summary of Contents for AMS Wireless Vibration Monitor
Page 1: ...User Guide MHM 97927 PBF Rev 1 August 2020 AMS Wireless Vibration Monitor User Guide ...
Page 42: ...Configuration User Guide August 2020 MHM 97927 PBF 42 MHM 97927 PBF Rev 1 ...
Page 50: ...Installation User Guide August 2020 MHM 97927 PBF 50 MHM 97927 PBF Rev 1 ...
Page 80: ...Product certifications User Guide August 2020 MHM 97927 PBF 80 MHM 97927 PBF Rev 1 ...
Page 82: ...Third party licenses User Guide August 2020 MHM 97927 PBF 82 MHM 97927 PBF Rev 1 ...
Page 85: ...User Guide MHM 97927 PBF August 2020 MHM 97927 PBF Rev 1 85 ...