WARNING!
•
The Trex unit cannot power a 4-wire device. Do not connect Trex unit to the power
terminals of a 4-wire device. This can blow a fuse inside the Trex unit. The repair/
replacement will need to be completed at an authorized service center.
•
Do not connect lead sets to the HART and HART + pwr terminals at the same time. If the
lead sets are connected to devices, this increases the chance of wiring mistakes and
could create a short in the HART loop.
•
Do not add any external power to the device when the Trex unit is powering the device.
This can blow a fuse inside the Trex unit. The repair/replacement will need to be
completed at an authorized service center. Ensure the device is disconnected from the
loop/segment and no other wires are connected to the device before providing power
from the Trex unit.
•
Do not use the Trex unit to power a
Wireless
HART device. Providing power to a
Wireless
HART device may damage the device.
•
Do not connect the mA terminals (ammeter) in parallel with a powered 4-20 mA current
loop. Ammeters have low resistance. This can disrupt the loop and cause devices to
report incorrect values or positioners to move unexpectedly.
•
Do not connect the mA terminals on the Trex unit to a power supply that is not current
limited to 250 mA. This can blow a fuse inside the Trex unit. The repair/replacement will
need to be completed at an authorized service center.
2.5.1
Ammeter on the Device Communicator Plus
communication module
The Device Communicator Plus communication module has several ammeters for reading
current:
1.
Ammeter in the mA terminals. This ammeter is intended for quick measurements
and is for reference only.
2.
Ammeter in the HART + pwr terminals. This ammeter is used when the Trex unit is
powering a transmitter. This ammeter is intended for tasks including digital-to-
analog trims where a higher accuracy ammeter is required.
3.
Ammeter in the HART + pwr and HART terminals. This ammeter is used when the
Trex unit is controlling current or is powering a positioner. The ammeter is intended
to give feedback on the output current from the Trex unit and is for reference only.
WARNING!
•
Do not use the HART + pwr and mA terminals in series when the Trex unit powers a
device.
•
Do not connect the mA terminals (ammeter) in parallel with a powered 4-20 mA current
loop. Ammeters have low resistance. This can disrupt the loop and cause devices to
report incorrect values or positioners to move unexpectedly.
•
Do not connect the mA terminals on the Trex unit to a power supply that is not current
limited to 250 mA. This can blow a fuse inside the Trex unit. The repair/replacement will
need to be completed at an authorized service center.
For best results when using the mA terminals, do the following:
AMS Trex Device Communicator overview
12
User Guide
Summary of Contents for AMS Trex
Page 1: ...User Guide Rev 3 August 2017 AMS Trex Device Communicator User Guide ...
Page 8: ...Contents vi User Guide ...
Page 130: ...Field Communicator application 122 User Guide ...
Page 186: ...Fieldbus Diagnostics application 178 User Guide ...
Page 198: ...Technical specifications 190 User Guide ...
Page 206: ...Glossary 198 User Guide ...